• Accuenergy

Acuvim-L Series
Multifunction Power Meters (Web Accessible – Panel Mount)

c/w Alarms, Max. & Min. Record and Power Quality Analysis for Commercial, Industrial and Utility Applications

cart Order online ►► | Acuvim-AL | Acuvim-BL | Acuvim-CL | Acuvim-DL | Acuvim-EL | Acuvim-KL |

DS6000 Video— Watch how to program the Acuvim-L series

Features

  • True-RMS measuring Parameters.
  • ANSI and IEC 0.2 Accuracy class.
  • Power Quality Analysis.
  • 4 Quadrant Energy.
  • Measure Individual Harmonics from 2nd to 15th (Acuvim-AL/BL/CL/DL).
  • Module Design (Acuvim-L/EL).
  • TOU, 4 Tariffs, 12 Seasons, 14 Schedules (Acuvim-EL).
  • Class leading Warranty.
  • IIII [+] Read More
    • Two (2) parameter Alarms
    • I/O module and Pulse Output option
    • Pulse Output option
    • Monitors Power Quality , Voltage Harmonics, Current Harmonics, Voltage Unbalance Factor, Current Unbalance Factor, Max/Min Statistics, Meter Running Time and Load Running Time

Applications

  • Metering of Distribution Feeders, Transformers, Generators, Capacitor Banks and Motors
  • Medium and Low Voltage Systems
  • Commercial, Industrial, Utility
  • Power Quality Analysis

Description

The Acuvim-L series is a range of economical yet highly functional three-phase multifunction power and energy meters manufactured by Accuenergy. These meters provide excellent value for monitoring power and energy management systems. The Acuvim-L series may be used as data gathering devices for intelligent power distribution or plant automation systems. All monitored data is available via a standard digital RS485 communication port running the Modbus RTU protocol. With a wide range of models to choose from, the Acuvim-L series offers unparalleled value and functionality.

IIII [+] Read More
Acuvim-L may be used as a data gathering device for an intelligent Power Distribution System or a Plant Automation System. All monitoring data is available via digital RS485 communication port running Modbus® Protocol. The quality of the power system is important with increasing use of electronic loads such as computers, ballasts or variable frequency drives. With the Acuvim-L power analysis option, any phase current or voltage can be displayed and the harmonic content calculated. By knowing the harmonic distribution, action can be taken to prevent overheated transformers, motors, capacitors, neutral wires and nuisance breaker trips. Redistribution of the system loading can also be determined.
 
  • Literature
  • Specifications
  • Model Selection
Literature and Technical Information
pdf icon

Multi-function Power Meters

++ Acuvim-L Series Specification Brochure | 870 kB
Specific Specifications
Model: Acuvim-AL | Acuvim-BL | Acuvim-CL | Acuvim-DL | Acuvim-EL | Acuvim-KL |
Model: Acuvim-L Power Meters – General Specifications
Real Time Metering
Phase Voltage: U1, U2, U3
Line Voltage: U12, U23, U31
Current: I1, I2, I3, In (Acuvim-KL no neutral current measurement)
Power: P1, P2, P3, Psum
Reactive Power: Q1, Q2, Q3, Qsum
Apparent Power: S1, S2, S3, Ssum
Power Factor: PF1, PF2, PF3, PF
Frequency: F Hz
Load Nature: L/C/R
Energy & Demand
Energy: Ep_imp, Ep_exp
Reactive Energy: Eq_imp, Eq_exp
Apparent Energy: Es
Current Demand: Dmd_I1,Dmd_I2 Dmd_I3
Power Demand: Dmd_Psum, Dmd_Qsum, Dmd_Ssum
TOU
Time of Use: Energy/Max Demand TOU, 4 Tariffs, 12 Seasons, 14 Schedules
Monitoring
Power Quality: Voltage Unbalance Factor: U_unbl
Current Unbalance Factor: I_unbl
Voltage THD: THD_V1, THD_V2, THD_V3
Current THD: THD_I1, THD_I2, THD_I3
Individual Harmonics: Harmonics 2nd to 31st
Statistics: Max Current Demand Dmd_I1_max,Dmd_I2 _max,Dmd_I3_max
Max Power Demand Dmd_Psum_max, Dmd_Qsum_max, Dmd_Ssum_max
Max & Min of Voltage  
Max & Min of Current  
Hour: Running Time Hour
Load Running Time Hour
I/O: Energy Pulse Output 2 DO, configured as pulse output for kWh and kvarh, the
pulse rate and width can be set
Alarm Output  
Options
Communication: RS-485 Modbus®-RTU Protocol, 1200~38400 baud rate
Second RS-485 Modbus®-RTU Protocol, 1200~38400 baud rate
Profibus PROFIBUS-DP/V0 Protocol
Extension I/O: 4DI, 2DO SOE, Pulse Counter, Pulse output, Alarm output
Accuracy Resolution and Range
Voltage: 0.5% 0.1V (20V~1000kV)
Current: 0.5% 0.001A (0~50000A)
Current Demand: 0.5% 0.001A (0~50000A)
Power: 0.5% 1W (-9999MW~9999MW)
Reactive Power: 0.5% 1var (-9999Mvar~9999Mvar)
Apparent Power: 0.5% 1VA (0~9999MVA)
Power Demand: 0.5% 1W (-9999MW~9999MW)
Reactive Power Demand: 0.5% 1var (-9999Mvar~9999Mvar)
Apparent Power Demand: 0.5% 1VA (0~9999MVA)
Power Factor 0.5% 0.001 (-1.0~1.0)
Frequency 0.5% 0.01Hz (45.00~65.00Hz)
Energy 0.5% 0.1kWh (0~99999999.9kWh)
Reactive Energy: 0.5% 0.1kvarh (0~99999999.9kvarh)
Apparent Energy: 0.5% 0.1VAh (0~99999999.9kVAh)
Harmonics: 1.0% 0.01%
Meter Running Time: 0.1hrs (0~999999999.9hrs)
Load Running Time: 0.1hrs (0~999999999.9hrs)
Specifications
Power Voltage: 100~415Vac, 50/60Hz; 100~300Vdc 50/60Hz
Withstand: 3250Vac, 50/60Hz for 1 minute
Temperature Range: - 25°C to 70°C
Storage Temperature: - 40°C to 85°C
Humidity Range: 5% to 95% Non-Condensing
Dimensions: 96×96×51mm (92×92 cutout) DIN
Compliance: Measurement Standard: IEC 62053-22; ANSI C12.20, 62053-23 Class 2
Environmental Standard: IEC 60068-2
Safety Standard: IEC 61010-1, UL 61010-1, IEC 61557-12
EMC Standard: IEC 61000-4/-2-3-4-5-6-8-11, CISPR 22, IEC 61000-3-2, IEC 61000-6-2/4
Outlines Standard: DIN 43700, ANSI C39.1
  ◎- OPTIONAL Acuvim
  Parameter -AL -BL -CL -DL -EL -KL
Real Time Metering: Phase Voltage
 
Line Voltage  
Current
Power
Apparent Power
Power Factor
Load Nature  
Energy  
 
Energy and Demand Energy
Reactive Energy
Apparent Energy
Current Demand
 
Power Demand  
Time of Use Energy          
Power Quality Voltage Unbalance
 
Current Unbalance  
Voltage THD  
Current THD
 
Individual Harmonics  
Statistics: Max Current Demand  
Max Power Demand  
Max & Min of Voltage  
Max & Min of Current  
Hour: Running Time
Load Running Time
     
 
I/O: Energy Pulse Output
         
Alarm Output
         
Communication: RS-485    
Second RS-485        
Profibus        
EXtension I/O: 4DI, 2DO