Voltage Transformers
GE / ITI 2VT460 Series – 3-Phase Voltage Transformers
- Frequency: 60 Hz
- Standard Secondary Voltage: 120 V
- Insulation Level: 600 V, BIL 10 kV
- Thermal Rating: 150 VA at 30C/100 VA at 55C
- Accuracy Class: 0.6 W, 1.2 X
GE / ITI 2VT469 Series – 3-Phase Voltage Transformers
- Frequency: 60 Hz
- Standard Secondary Voltage: 120 V
- Insulation Level: 600 V, BIL 10 kV
- Thermal Rating: 40 VA at 30C/27 VA at 55C
- Accuracy Class: + 1% at all burdens up to 5 VA at 1.0 and 0.95 P.F.
GE / ITI 3VT468 Series – 3-Phase Voltage Transformers
- Frequency: 60 Hz
- Standard Secondary Voltage: 120 V
- Insulation Level: 600 V, BIL 10 kV
- Thermal Rating: 75 VA at 30C/50 VA at 55C
- Accuracy Class: ± 0.6% @ 7.5 VA
GE / ITI 3VT471 Series – 3-Phase Voltage Transformers
- Frequency: 60 Hz
- Standard Secondary Voltage: 120 V
- Insulation Level: 600 V, BIL 10 kV
- Thermal Rating: 40 VA at 30C/27 VA at 55C
- Accuracy Class: ±1% @ 5 VA
GE / ITI PT6 Series – Indoor Medium Voltage Transformers
- Frequency: 60 Hz
- Maximum System Voltage: 25.5 kV, BIL 125 kV
- Thermal Rating: 1500 VA at 30C/1000 VA at 55C
- Accuracy Class: 0.3 WXMY,1.2 Z at 100 % rated voltage with 120 V based ANSI burden.
0.3 WXMY, 1.2 MY at 58 % rated voltage with 69.3 V based ANSI burden.
GE / ITI PTG3 & PTW3 Series – Indoor Medium Voltage Transformers
- Frequency: 60 Hz
- Maximum System Voltage: 5.6 kV, BIL 60 kV
- Thermal Rating: 750 VA at 30C/500 VA at 55C
- Accuracy Class: 0.3 WXMY,1.2 Z at 100 % rated voltage with 120 V based ANSI burden.
0.6 WX, 1.2 MY at 58 % rated voltage with 69.3 V based ANSI burden.
GE / ITI PTG4 & PTW4 Series – Indoor Medium Voltage Transformers
- Frequency: 60 Hz
- Maximum System Voltage: 9.52 kV, BIL 75 kV
- Thermal Rating: 1500 VA at 30C/1000 VA at 55C
- Accuracy Class: 0.3 WXMY,1.2 Z at 100 % rated voltage with 120 V based ANSI burden.
0.3 WXMY, 1.2 MY at 58 % rated voltage with 69.3 V based ANSI burden.
GE / ITI PTG5 & PTW5 Series – Indoor Medium Voltage Transformers
- Frequency: 60 Hz
- Maximum System Voltage: 15.5 kV, BIL 110 kV
- Thermal Rating: 1500 VA at 30C/1000 VA at 55C
- Accuracy Class: 0.3 WXMY,1.2 Z at 100 % rated voltage with 120 V based ANSI burden.
0.3 WXMY, 1.2 MY at 58 % rated voltage with 69.3 V based ANSI burden.
GE / ITI 3VT472 Series – 3-Phase Voltage Transformers
- Frequency: 60 Hz
- Standard Secondary Voltage: 120 V
- Insulation Level: 600 V, BIL 10 kV
- Thermal Rating: 40 VA at 30C/27 VA at 55C
- Accuracy Class: ± 1% @ 5 VA
GE / ITI 3VTL460 Series – 3-Phase Voltage Transformers
- Frequency: 60 Hz
- Standard Secondary Voltage: 120 V line-to-line
- Insulation Level: 600 V, BIL 10 kV
- Thermal Rating: 150 VA at 30C/100 VA at 55C
- Accuracy Class: 0.6 W, 1.2 X at 60 Hz
GE / ITI 3VTN460 Series – 3-Phase Voltage Transformers
- Frequency: 60 Hz
- Standard Secondary Voltage: 120 V
- Insulation Level: 600 V, BIL 10 kV
- Thermal Rating: 150 VA at 30C/100 VA at 55C
- Accuracy Class: 0.6 W, 1.2 X at 60 Hz
GE / ITI 450 Series – Voltage Transformers
- Frequency: 60 Hz
- Standard Secondary Voltage: 120 V
- Insulation Level: 600 V, BIL 10 kV
- Thermal Rating: 750 VA at 30C/500 VA at 55C
- Accuracy Class: 0.3 W, X, M & Y, 1.2Z
Those marked ** are 0.3 W, 0.6 X, M & Y
GE / ITI 450I Series – IEC Rated 50 Hz Voltage Transformers
- Frequency: 50 Hz
- Standard Secondary Voltage: 110 Volts
- Insulation Level: 720 Volts
- Accuracy Class: 0.2 at 40 VA / 0.5 at 70 VA
- Thermal Rating: 550 VA at 30C / 350 VA at 55C
GE / ITI 460 Series – Voltage Transformers
- Frequency: 60 Hz
- Standard Secondary Voltage: 120 V
- Insulation Level: 600 V, BIL 10 kV
- Thermal Rating: 150 VA at 30C/100 VA at 55C
- Accuracy Class: 0.6 W, 1.2 X at 60 Hz
GE / ITI 460I Series – IEC Rated 50 Hz Voltage Transformers
- Frequency: 50 Hz
- Standard Secondary Voltage: 110 Volts
- Insulation Level: 720 Volts
- Accuracy Class: 0.5 at 10 VA / 1.0 at 20 VA
- Thermal Rating: 125 VA at 30C / 75 VA at 55C
GE / ITI 465 Series – Voltage Transformers
- Frequency: 60 Hz
- Standard Secondary Voltage: 120 V
- Insulation Level: 600 V, BIL 10 kV
- Thermal Rating: 150 VA at 30C/100 VA at 55C
- Accuracy Class: 0.6 W, 1.2 X at 60 Hz
GE / ITI 467 Series – Voltage Transformers
- Frequency: 60 Hz
- Standard Secondary Voltage: 120 V
- Insulation Level: 600 V, BIL 10 kV
- Thermal Rating: 40 VA at 30C/27 VA at 55C
- Accuracy Class: ± 1% at all burdens up to 5 VA at 1.0 and 0.95 P
GE / ITI 475 Series – Voltage Transformers
- Frequency: 60 Hz
- Standard Secondary Voltage: 120 V
- Insulation Level: 600 V, BIL 10 kV
- Thermal Rating: 300 VA at 30C/200 VA at 55C
- Accuracy Class: 0.3 W, 0.6 X, 1.2 M at 60 Hz
GE / ITI 475I Series – IEC Rated 50 Hz Voltage Transformers
- Frequency: 50 Hz
- Standard Secondary Voltage: 110 Volts
- Insulation Level: 720 Volts
- Accuracy Class: 0.2 at 10 VA / 0.5 at 20 VA
- Thermal Rating: 225 VA at 30C / 150 VA at 55C
GE / ITI JE-27C Series – Indoor Voltage Transformers
- Frequency: 60 Hz
- Insulation Level: 600 Volts, BIL 10 kV
- Primary Voltage: 69.3-600 V
- Thermal Rating: 150 VA at 30C / 100 VA at 55C
GE / ITI JEV-0C Series – Indoor Voltage Transformers
- Frequency: 60 Hz
- Insulation Level: 600 Volts, BIL 10 kV
- Primary Voltage: 69.3-600 V
- Thermal Rating: 300 VA at 30C / 200 VA at 55C
GE / ITI JVA-0C Series – Indoor/Outdoor Voltage Transformers
- Frequency: 50-60 Hz
- Insulation Level: 600 Volts, BIL 10 kV
- Primary Voltage: 120-600 V
- Thermal Rating: 500 VA at 30C / 300 VA at 55C
GE / ITI JVF-0C Series – Indoor/Outdoor Voltage Transformers
- Frequency: 50-60 Hz
- Insulation Level: 600 Volts, BIL 10 kV
- Primary Voltage: 120-600 V
- Thermal Rating: 300 VA at 30C / 200 VA at 55C
GE / ITI JVM-0C Series – Indoor/Outdoor Voltage Transformers
- Frequency: 60 Hz
- Insulation Level: 600 Volts, BIL 10 kV
- Primary Voltage: 69.3-600 V
- Thermal Rating: 750 VA at 30C / 500 VA at 55C
GE / ITI JVM-2C/3C Series – Indoor Voltage Transformers
- Frequency: 50-60 Hz
- Insulation Level: BIL 60 kV
- Voltage: 2,400-4,800 V
- Thermal Rating: 750 VA at 30C/500 VA at 55C
GE / ITI JVM-4AC/5AC Series – Indoor High Accuracy Voltage Transformers
- Frequency: 50-60 Hz
- Insulation Level: BIL 75-110 kV
- Voltage: 4,200-14,400 V
- Thermal Rating: 2,000 VA at 30C/1,400 VA at 55C
GE / ITI JVM-4C/5C Series – Indoor Voltage Transformers
- Frequency: 50-60 Hz
- Insulation Level: BIL 75-110 kV
- Voltage: 4,200-14,400 V
- Thermal Rating: 1,500 VA at 30C/1,000 VA at 55C
GE / ITI JVW-110C Series – Outdoor High Accuracy Voltage Transformers
- Frequency: 60 Hz
- Insulation Level: 15.5 kV, BIL 110 kV
- Primary Voltage: 7,200-14,400 V
- Thermal Rating: 1,000 VA at 30C/750 VA at 55C
GE / ITI JVW-5AC-1 Series – Outdoor High Accuracy Voltage Transformers
- Frequency: 60 Hz
- Insulation Level: 15.5 kV, BIL 110 kV
- Primary Voltage: 7,200-14,400 V
- Thermal Rating: 1,500 VA at 30C
GE / ITI JVW-5C Series – Outdoor Voltage Transformers
- Frequency: 60 Hz
- Insulation Level: 15.5 kV, BIL 110 kV
- Primary Voltage: 7,200-14,400 V
- Thermal Rating: 1,500 VA at 30C