AEMC Model 6416 (Clamp-On)

Ground Resistance Tester

space
space
Model 6416 Ground Resistance Tester (Clamp-On)
Characteristics:
  • Touch voltage is displayed to alert user to potential unsafe conditions
  • Large multi-function, bright yellow organic display (OLED) is visible in all lighting conditions
  • Selectable test frequency improves accuracy in inductive environments
  • Differentiates between loop and ground resistance measurements
  • Data storage (Ω, A,V and µH with time-stamping): Stores up to 300 measurements
  • Easy clamp opening via a force compensation trigger system with 35mm clamp diameter
  • Test frequency selection provides more accurate results in inductive environments
  • Touch voltage indication indicates the voltage on the display along with a warning buzzer when the voltage derived from current and resistance measurements detect a potentially dangerous touch condition
  • Loop resistance indication alerts the user to the fact that the measurement may not be ground resistance
Application:
  • Ground electrode system resistance
  • Bonding/continuity checks
  • Cell tower grounding verification
  • Ground measurements on Railroad signaling systems
Product Description:     space

The Clamp-on Ground Resistance Tester Model 3731 measures ground rod and small grid resistance through any season, without the use of auxiliary ground rods.Check Resistance on Single and Multiple Rods or Grids.

The Ground Resistance Tester Model 6416 measures ground rod and grid resistance and impedance without the use of auxiliary rods. Clamp-on ground resistance testers can be used in multi-grounded systems without disconnecting or de-energizing the ground system under test it. The Model 6416 simply clamps around the grounding electrode or conductor and measures the resistance to ground. By performing measurements on intact ground systems, the user also verifies the quality of the grounding connections and bonds. Resistance and continuity of grounding loops around pads and buildings may also be measured.

The Model 6416 includes a high sensitivity measurement function enabling measurement of leakage current flowing to ground or circulating in ground loops from 0.2mA to 40A and resistances from 0.01 to 1500Ω. It also offers battery life information at power-up and Auto Power OFF power management. The Buzzer and Auto Power OFF features may be disabled at any time.

space
Specifications:
space
ELECTRICAL Model 6416
Ground Resistance Range Resolution Accuracy
Auto-Ranging 0.1 to 199Ω 0.010 to 0.099Ω 0.001Ω ±1.5% ± 0.01Ω
0.10 to 0.99Ω 0.01Ω ±1.5% ± 0.02Ω
1.0 to 49.9Ω 0.1Ω ±1.5% ± 0.1Ω
50 to 99.5Ω 0.5Ω ±2% ± 0.5Ω
100 to 199Ω ±3% ± 1Ω
200 to 395Ω ±5% ± 5Ω
400 to 590Ω 10Ω ±10% ± 10Ω
600 to 1150Ω 50Ω 20% approx
1200 to 1500Ω 50Ω ±25% approx
Current Measurement 0.200 to 0.999mA 1µA ±2% ± 50µA
Auto-Ranging 1mA to 40As 1000 – 2.990mA 3.00 – 0.99mA 10µA ±(2% + 50µA)
10.0 – 29.90mA 30.0 – 99.9mA 100µA ±(2% + 100µA)
100.0 – 299.0mA 0.300 – 0.990A 1mA ±(2% + 1mA)
1.000 – 2.990A 3.00 – 39.99A 10mA ±(2% + 10µA)
Selectable Measurement Frequency 50,60,128 or 2083Hz
Current Measurement Frequency 47 to 800Hz
Inductance Measurement 10 – 100µA 100 – 500 µA
Current Overload OL displayed above 39.99Arms
Power Source 4×1.5V LR6 (AA) Alkaline or 4 NiMH batteries Battery life: 12 hours or 1440 30-second measurements approx.