Display |
Scaling: |
Customized to any scaling desired, from linear to specialized Cos Ø, square root distributions, with color applications for visual emphasis and to any desired engineering unit. |
Specific accuracies |
Basic Accuracy: |
±2% of full scale basic accuracy class. |
Rectifier Meters: |
±2% @ 25°C calibrated to sine wave. |
Power Factor: |
0.025% @ 0.5 PF , 0.007% @ 1.0 PF |
Expanded Scale: |
3% of frequency span |
|
Position of use: |
Vertical (scale) standard
or to specified angle or position |
Full scale deflection angle: |
250°, except synchroscope is 360° |
Full scale length: |
6.9 inches. |
Movement: |
Proven, shock resistant Taut Band |
Case: |
All switchboard instruments have drawn steel case |
Cover: |
polycarbonate cover and window. |
Terminal plate: |
phenol resin material. |
Mounting studs: |
1/4” x 28 thread. |
Terminal studs: |
10-32 thread. |
Dielectric level: |
2500VAC for 1 minute between the electrical circuit and mounting
studs. |
Overload rating: |
Voltmeter and potential coils-1.2 x rating (continuous).
AC Ammeters- 2 x rating (continuous), and 10 x rating for one second.
Current coils (other than ammeters) 1.5 x rating (continuous), and 10 x
rating for one second. |
Response time: |
Approximately 3 seconds |
General: |
Operating Temp.: |
0 to 40°C (32 to 104°F) |
Storage Temp: |
-10 to 50°C (14 to 50°F) |
Extreme temperature range: |
-20°C to 65°C (-4 to 149°F)
Tropicalized or IP54 sealed units available |
Relative Humidity: |
95% (non condensing) |