Yokogawa PR201 Moniteurs de Puissance Switchboard Multifonctionels

space
Yokogawa PR201 Digital Power Monitors
cart Order YOKOGAWA TMI Products on-line
 Characteristics:
  • Sharp and large 5-digit LED display with 20mm digit.
  • 1-phase 2-wire, 1-phase 3-wire, 3-phase 3-wire & 3-phase 4-wire models are available.
  • Wide variety of measurement items Integrated power, optional integrated power, instantaneous power, voltage (instantaneous, maximum & minimum values), current (instantaneous & maximum values) and power factor (optional feature) are available
  • Wide display range, unit of W, kW & MW by LED indicator
  • Fully supported communication function RS485 communication (MODBUS and PC-link protocols are supported) and LON communication can be optionally selected.
  • Easy to set and maintain CT-ratio, PT-ratio, integrated low-cut power, etc. by front-panel key switch.
Product Description:
space
The PR201 Power Monitor (for switchboard mounting type) can help energy saving, thus reducing cost, and also help diagnose electrical equipment. PR201 has the same barrel mounting as 4-1/2″ switchboard meter for easy replacement of existing meters. It measures electric energy (power) consumed by electrical equipment and displays the value as the integral power consumption. It also displays instantaneous power, voltage, current, power factor, etc. For optional output function, 4 to 20mA analog output for instantaneous power value or integrated pulse output is available. For optional communication function, RS485 or LON communication interface is available.
space
Specifications :
space
Display
Display: 7-segment LED as its display.
Digit height: 0.56” high digits
Color: Red
Range: -99999 to +99999
Number of Digits: 5 digits
Measuring Function: Accuracy:
Instantanous power, voltage r.m.s. value, current r.m.s. value: ±0.5% of rated value (at 23°C±2°C)
Integrated power energy: ±0.5% of rated value (at 23°C±2°C)
Active power : ±2% of rated value (at 23°C±2°C)
Analog Output : ±0.5% of span (at 23°C±2°C)
Insulation resistance: 100 MΩ minimum (at 500 V DC)
Withstand voltage: 2000 V AC for 1 minute
output -1000 V AC for 1 minute
output -500 V AC for 1 minute, between optional integrated control signal and (input, output, communication output, power supply and ground)
Impulse withstand voltage: 5kV (1.2/50μs)
Analog Output
Allowable load resistance : 0 to 750Ω
Output Signal : 4 to 20 mA DC
Pulse Output:
No. of outputs: 1
Output signal: Open collector
Contact capacity: 30 V DC, 200 mA
Pulse unit: Indicates actual kWh corresponding 1 pulse input to this instrument.
Communications:
Serial Bus: RS-485 communication
LON Communication: Measuring data can be simply read out on personal computer through LON communication adapter and DDE: server without consciousness of communication. Also, control of optional integration and initaialization of maximum and minimum values can be done through personal computer.
General
Safety standards: Compliant with IEC/EN61010-1 Under application for UL611010 approvale
Power source: 85 to 264V AC, 45 to 65Hz
Power dissipation: 6VA (at 100V AC) 8VA (at 200V AC)
Operating Power -10 to 55°C
Storage Temp. : -20 to 70°C
Ambient humidity: 5 to 90% RH (no condensation)
Case: Polycarbonate resin (PC), UL94 V-0 Dustproofness and dripproof IP5X
Terminal block: Polybutylene terephthalate (PBT), UL94 V-0
Terminal cover: Polyamide resin (PA6), UL94 V-2
Dimensions: 110 x 110 x 128 mm (H x W x D)
Weight: Approx. 600 g
space
pdf_pic Downloads: General Specifcations
space
Related urls:
weblink
base
mail web