• YOKOGAWA

Model CL150, AC Current (0-200-600A),
AC Voltage Mean Value Clamp-on Meters

ACA, ACV, DCV, Ohm, Continuity Check Clamp-on Tester for AC Current
(for conductors up to 54 mm in diameter)
Yokogawa CL150 Clamp-on Meters
Features
  • 3 1/2 digit LCD display
  • AC current measurement with current ranges up to 2000A
  • Mean value display
  • AC/DC voltage and resistance measurements
  • DC output
  • 54mm in diameter of measurable conductor
  • Mean value display
  • DC output function
  • Data hold function
  • Sleep function
  • Approved for conformity to safety standards:
    EN61010-1,EN61010-2-031, EN61010-2-032 (CAT. III 600 V, CAT. II 1000 V)

* All Clamp-on Meters include Test Leads (where applicable) and a carrying case

cart Please contact a sales person for price and delivery ►►

Applications

  • Preventative maintenance
  • Testing for current leakage on branch circuits
  • Measuring current draw of motors and motor control circuits
  • Measuring Loads

Description

The CL150 is a versatile and highly accurate Clamp-on meter with a array of features ideal for most applications. This unit is rugged, reliable and cost effective. Jaws accommodate up to 30mm conductors.
  • Literature
  • Specifications
Literature and Technical Information
pdf icon

Clamp-on Meters – Portable Test Instruments

++ CL150 Clamp-on Meters| Specification sheet
Model: Yokogawa CL150 Clamp-on Meters
Display
Display LCD (Digital display:1999 counts)
Specific Accuracies
AC Accuracy (400A): 1.0+3(50/60Hz)
2.0+3(40~1kHz)
AC Accuracy (2000A): 1.0+3(50/60Hz)
3.0+3(40~1kHz)
AC Voltage Accuracy (40/400V/750V) 1.0+2(50/60Hz)
1.5+3(40~1kHz)
DC Voltage Accuracy (40/400V/1000V) 1.0+2
Resistance Accuracy (400/4k/40k/400kΩ) 1.5+2, Beeps at below 50± 35Ω (continuity check)
DC Output Accuracy (400A, 0~400mV) .5۫% rdg ± 0.5mV (50/60Hz)
.5% rdg ± 0.5mV (40~1kHz)
General specifications
Crest Factor (50/60Hz)
Frequency Accuracy 1.2+4, Beeps at below 30Ω (continuity check)
Method of detection Mean Value
Response Time Approx. 2 seconds
Range Switching Manual-range (on AC current range) / Auto-range (on AC voltage range, resistance range)
Data Hold On all range
Peak Hold On all range
Influence of external magnetic field 1A or less at 400A/m
Influence of conductor position ± (2% rdg + 3dgt) or less
Safety Standard Conforms EN 61010-1, EN61010-2-031, EN61010-2-032
Circuit Voltage 1000Vrms or less
Withstanding Voltage 5.55kV AC for one minute
Sleep Function Automatically powered down in about 10 minutes after the last switch operation
Diameter of measurable conductor 54mm at maximum
Environment
Operating temperature: 0-40°C
Relative Humidity: 85% RH or less (no condensation)
Dimensions Approx. 105(W) x 247(H) x 49(D)mm
Weight Approx. 470g
Accessories Clamp Adapter (Model 99025), Output Cable for Terminal Screw (Model 91019), Carrying Case (Model 93034), Output Plug (Model 98012), Test Lead (Model 98011), User’s manual (IM CL150), batteries
Power Supply R6P(SUM-3)x2 or LR6x2
Battery Life Approx. 150 hours (continuous)
Consumed Current Approx. 5mA