• RISHABH

Rish CON-I Current Transducer Series

Digital Utility CURRENT Transducer for Power Management Applications
Rishabh Rish CON-I Digital Current Transducer series

Features

  • True RMS measurement
  • On-site programmable current (CON-I) range
  • On-site selectable output type (dc voltage/ dc current)
  • Single or dual output
  • Accuracy class 0.2 (IEC/EN 60688)
  • 7 segment LCD display
  • RS-485 (Mobus) Communications
  • Wide auxiliary power supply (60V-300V) AC & DC
  • Output Response time <300 ms
  • DIN rail installation
IIII [+] Read More
  • Measuring input: AC Current, sine wave or distorted waveform
  • Analog output (single or dual) – isolated analog output programmable
  • Programmable input/output
  • RS-485 communication
  • LED indication: Power on and output output option 1: Red LED output option 2: green LED

Applications

  • Generation and Industrial applications – measuring power quantities and providing a proportional (real-time) analog signal
  • Manufacturing and OEM Application

Description

The Rish CON-I transducer series measures and convert ac current to dc process signals for direct input into monitoring systems such as recorders, data acquisition systems, panel monitoring instruments etc. The CON-I transducers process True RMS signals, providing accurate readings for signals that contain harmonic distortion. The input signal is converted into a load independent signal and the output signal generated is proportional to the mean root square value of the input current value.
IIII [+] Read More
The Rish CON-I transducer series is available with an optional 7 segment LCD and keypad interface that allows the user to configure the transducer input on-site. The RS485 port allows the user to configure or read measured parameters remotely. These transducers are precision engineered to provide superior accuracy , reliability and manufactured from finest materials and components for long-term performance.
  • Literature
  • Specifications

Literature and Technical Information

pdf icon

Signal Modifiers

++ RISH CON-I Series – Current Transducers
Model: Rishabh RIS CON-P Power transducer
Specific Accuracies
Current: ±0.2% accuracy
Measuring Input
Current (AC RMS) Transducer 1 A ≤ IN ≤ 5 A
PT Primary range: 1 A – 9999 A
Nominal Frequency (FN) 50 Hz or 60 Hz
Nominal input Voltage Burden: < 0.2 VA IN
Overload Capacity: 1.2 * IN current continuously 10 * IN current for 3 seconds, repeated 5 times in a 5 minute interval 50 * IN bcurrent for 1 seconds, repeated 1 times in a 1 hour interval
Measuring Input
Low independent DC output: Unipolar: 0…20mA, 4…20mA or 0…10V Bipolar: -20mA…0..+.20mA, 4…20mA or -10…0…+10V
Output Burden – DC Current output: 0 ≤ R ≤ 15 V/(end value of dc output)
Current Limit Under Load ≤1.25 * (end value of dc output) – with current output ≤100mA with voltage output
Response Time: 300 ms
General Specifications
Protection Class: II (Protection isolation, EN 61010)
Case rating: IP40 housing, EN 60 529 IP20 terminals EN 60 529
Case Materials: Lexan 940 (polycarbonate) Flammability class: UL 94 self extinguishing
Insulation Category: 50Hz, 1 minute (EN 61010-1) 5500V input versus outer surface 3700V input versus all other circuits 3700V auxiliary power supply versus outer surface and output
Mounting: Rail Mounting, wall mounting
Weight: approx. 04kg
Environmental
Operating Temp.: 0 to 23°C to 45°C
Storage Temp: -40°C to 70°C
Relative Humidity: ≤ 75% (non condensing)
Frequency Range: 10Hz …150Hz …10Hz
Ambient Tests: EN 60 068-2-6 (Vibration), EN 60 068-2-7 (Shock), EN 055 011[IEC 1000-4-2/-3/-4-6] Electro-magnetic compatibility, EN 60 068-2-1/-2/-3 cold, dry, damp heat