header

AEMC®Instruments

Model 514 [Catalog No. 2117.70]

Clamp-on Meters
previous URL Next URL
< Links >
AEMC® Model 514 Clamp-On Meters
Characteristics:
  • Standard size, full function Clamp-on meter
  • 1000AAC current measurements
  • 750VAC/1000VDC volt measurements
  • True RMS meassurements
  • Resistance measurement to 4000Ω
  • Continuity with beeper below 40Ω
  • Frequency measurements from V and A
  • Diode test
  • 1ms Peak function for fast capture of signals
  • Ideal for inrush measurement
  • Hold function to “freeze” readings
  • Push-button for easy ADC zeroing
  • Large easy-to-read 4000-count display
  • 42-segment analog bargraph
  • Includes test leads and soft carrying pouch
Application:
  • Commercial, industrial, residential and HVAC troubleshooting
  • Power panel, junction box and battery bank monitoring
  • AC or DC motor testing
  • Power plant troubleshooting
  • Electrical testing and troubleshooting on non-linear loads, such as adjustable speed drives and computers
Product Description:
space The Model 514, Clamp-on Meter, is a general purpose professional Clamp-on meter that measures up to the toughest standards. It is built into a rugged mechanical case and is designed using quality polycarbonate materials. This meter offers a complete set of measurement ranges and is in compliance with international safety and quality standards to ensure a professional and reliable measuring tool. The Model 514 is auto-ranging and provides the best measurement range and resolution for troubleshooting. It has a high resolution 40A range.The Model 514 measures AC Amps, AC Volts, DC Volts, Ohms, Continuity (with beeper), Frequency (from V or A) and has a Diode Test function. The Model 514 also uses Hall sensor technology that provides both DC and AC current measurements to 1000A. The Model 514 is sized for a comfortable, one-handed operation. This model is average sensing and designed for traditional average responding electrical systems. The jaw opening for the Model 514 is 1.575″ (40mm).
Specifications:
True RMS Model 514
AC AMPERES
Measurement Range 0.05A to 1000A
Resolution 40A400A 1000A 0.01A0.1A 1A
Accuracy 50 to 60Hz60 to 500Hz ±1.9% of Reading ± 5cts±1.9% of Reading ± 5cts
Overload Protection 40A400A 1000A 800Arms1500Arms 1500Arms
AC VOLTS
Measurement Range 0.5V to 750V
Resolution 400V750V 0.1V1V
Accuracy 50 to 500Hz ±1.2% of Reading ± 5cts
Input Impedance 1MΩ
Overload Protection 1000Vrms
DC AMPERES
Measurement Range 1A to 1000A
Resolution 40A400A 1000A 0.01A0.1A 1A
Accuracy ±2.5% of Reading ± 10cts
Overload Protection
1200Arms
DC VOLTS
Measurement Range 0.2 to 600V
Resolution 400V600V 0.1V1V
Accuracy ±0.75% of Reading ± 2cts
Input Impedance
10MΩ
Overload Protection
1200Vrms
RESISTANCE-OHMS (Ω)
Measurement Range 0.2 to 4000Ω
Resolution 400Ω4000Ω 0.1Ω1Ω
Accuracy ±1% of Reading ± 2cts
Max Test Voltage
3 VDC
Overload Protection
600Vrms
DIODE
Test Current 0.6mA
Overload Protection 600Vrms
Open Circuit Voltage 3 VDC
CONTINUITY
Beeper Activation <40Ω
Max. Test Voltage 3 VDC
Overload Protection 600Vrms
FREQUENCY (Hz)
CURRENT INPUT
Range
4kHz10kHz 1Hz Resolution10Hz Resolution
Accuracy (20Hz to 10kHz) ±0.1% of Reading ± 1ct
Min Input Signal
4kHz10kH 2Arms5Arms
VOLTAGE INPUT
Range
4kHz40kHz
1Hz Resolution10Hz Resolution
Accuracy (20Hz to 10kHz)
±0.1% of Reading ± 1ct
Min Input Signal
4kHz40kHz
5Vrms5Vrms
General Specifications
Digital Display 3 3/4 digits LCD display, 4000-count (max. reading 3999)
Analog Display Fast 42-segment analog bargraph display
Symbol & Scale Range Automatic according to range and input signal
Polarity Displayed when negative signal applied to input
Overload Displayed when input signal exceeds range
Sample Rate 2 samples/sec for the digital display, 20 samples/sec for the analog bargraph
Power Source 9V, NEDA 1604 or 6F22 or 006P
Auto-Off 30 minutes
Low Power Indication Displayed when the battery is below the required voltage
Jaw Opening Size Ø 1.575″ (40mm) – faciliates 750MCM cable or two 500MCM cab
Dimension 9.53 x 2.60 x 1.42″ (242 x 66 x 36mm)
Weight 14.10 oz (400g) with batteries
ENVIRONMENTAL
Altitude 2167 ft (2000m) max.
Operating Temperature 32° to 104°F (0° to 40°C),<80% RH, non-condensing
Storage Temperature 14° to 140°F (-10° to 60°C),<70% RH, battery removed
Pollution Degree 2
SAFETY
Safety Rating EN 61010, 600V Cat. II, EN 61010, 10000V Cat. III
CE Mark Yes
Downloads:
pdf_pic Downloads: Specifications