AEMC®Instruments

Model 500 [Catalog No. 2117.54]

Clamp-On Meters

space

AEMC® Model 500 Clap-On Meters

Characteristics:

  • Compact size – fits into your pocket
  • 400AAC current measurements
  • 600VAC volts measurements
  • Resistance measurements to 400Ω
  • Continuity with beeper below 35Ω
  • Hold function to “freeze” readings
  • Large easy-to-read 4000-count display
  • 42-segment bargraph
  • Includes test leads and a soft carrying pouch

Application:
  • Electrical testing of distorted currents found on uninterruptible power supplies (UPS), speed controls, static power blocks, chopped power supplies, controllers and motors
Product Description:
space
space The Model 500, Clamp-On Meter, is a general-purpose professional clamp-on. A strong mechanical case design, quality materials, full ranges and compliance to international safety and quality standards ensures for a professional and reliable tool.The Model 500 is auto-ranging, and provides the user with AC Volts, AC Amperes, resistance, and continuity. The large and complete 4000-count LCD and features comprehensive user interface symbols such as a low battery indicator. It is equipped with a Data Hold functions. The Model 500 is compact for comfortable one-handed operation, and the hooked jaw design is easy to maneuver in crowded wiring and breaker panels. The jaw opening for the Model 500 is 1.1” (28mm).
Specifications:
space
Average Sensing Model 500
AC AMPERES
Measurement Range 0.05 to 400A
Resolution 40A400A 0.01A0.1A
Accuracy 50 to 60Hz60 to 500Hz ±2% of Reading ± 5cts±2.8% of Reading ± 5cts
Overload Protection 600Arms
AC VOLTS (Auto-Ranging)
Measurement Range 0.5 to 600V
Resolution 400V600V 0.1V1V
Accuracy 50 to 60Hz60 to 500Hz ±1% of Reading ± 5cts±1.5% of Reading ± 5cts
Input Impedance 1MΩ
Overload Protection 600Vrms
RESISTANCE-OHMS (Ω)
Measurement Range 0.3 to 400Ω
Resolution 0.1Ω
Accuracy ±1.9% of Reading ± 3cts
Max Test Voltage
1.5VDC
Overload Protection
600Vrms
CONTINUITY
Beeper Activation <35Ω
Max. Test Voltage 1.5VDC
Max Test Voltage
600Vrms
General Specifications
Digital Display 3 3/4 digits LCD display, 4000-count (max. reading 3999)
Analog Display Fast 42-segment analog bargraph display
Symbol & Scale Range Automatic according to range and input signal
Polarity Displayed when negative signal applied to input
Overload Displayed when input signal exceeds range
Sample Rate 2 samples/sec for the digital display, 20 samples/sec for the analog bargraph
Power Source Two 1.5V AAA batteries
Auto-Off 30 minutes
Low Power Indication Displayed when the battery is below the required voltage
Jaw Opening Size Ø 1.1″ (28mm) – faciliates 500MCM cable
Dimension 7.60 x 1.97 x 1.1″ (193 x 50 x 28mm)
Weight 8.11 oz (230g) with batteries
ENVIRONMENTAL
Altitude 2167 ft (2000m) max.
Operating Temperature 32° to 104°F (0° to 40°C), <80% RH, non-condensing
Storage Temperature 14° to 140°F (-10° to 60°C), <70% RH, battery removed
Pollution Degree 2
SAFETY
Safety Rating EN 61010, 600V Cat. II, EN 61010, 300V Cat. III
Double Insulation Yes
CE Mark Yes