- 4-quadrant Energy
- Energy Time of Use(TOU)
- Energy Reading
- Power Quality Analysis
- Waveform Capture
- Trend Record
- Sequence of Even(SOE)
- Over limit alarm
- Switch statues monitoring
- Remote switch controlling
Metering
- Voltage V1, V2, V3, Vlnavg, V12, V23, V31, Vllavg
- Current I1, I2, I3, In, Iavg
- Power P1, P2, P3, Psum
- Reactive Power Q1, Q2, Q3, Qsum
- Apparent Power S1, S2, S3, Ssum
- Power Factor PF1, PF2, PF3, PF
Monitoring
- Power Quality
- Demand
- Energy (Time of Use)
- Trend
- Alarm
- Max / Min.
Alarms
- Up to 16 groups of alarm events could be recorded. The
monitoring objects can be chosen from 242 metering parameters.
Maximum 16 group alarm inequations can be set and logic relation
between inequations can be used. The alarm event can be used to
trigger Digital Output or Relay Output even Waveform Capture.
I/O
- 4 Digital Input (DI)
- 2 Relay Output (RO)
- 2 Digital Output (DO)
- RO/DO Related
Display
- Clear and large character LCD Screen display with blue back light
|
|
|
|
|
|
|
|
|
|
- Medium and low voltage systems
- Commercial, industrial, utility
- Power quality analysis
|
|
|
|
|
|
|
 |
|
 |
The Acuvim-X high-end multifunction power meters can
monitor and control complex power distribution system.Acuvim-X may be used to gather data from intelligent
Power Distribution Systems . All Data can be accessed via 485 communication
port running Modbus™ Protocol. Optional Ethernet , Profibus DP
communication and wireless
transmission add flexibility to all your application needs. |
|
|
 |
|
|
|
 |
|
|
Metering |
Parameters |
Accuracy |
Resolution |
Range |
Voltage |
0.2% |
0.1V |
20V~500kV |
Current |
0.2% |
1mA |
5mA~50000A |
Power |
0.5% |
1W |
-9999~9999MW |
Apparent Power |
0.5% |
1VA |
0~9999MVA |
Energy |
0.5% |
0.1kWh |
0~99999999.9kWh |
Reactive Energy |
0.5% |
0.1kvarh |
0~99999999.9kVarh |
Apparent Energy |
0.5% |
0.1kVAh |
0~99999999.9kVAh |
Frequency |
0.2% |
0.01Hz |
45~65Hz |
Energy |
0.5% |
1W |
0~9999MW |
Reactive Energy |
0.5% |
0.1var |
0~9999MVar |
Apparent Energy |
0.5% |
0.1VA |
0~9999MVA |
Harmonics |
0.5% |
0.1% |
0~100.0% |
THD |
1.0% |
0.01% |
0~100.0% |
Running Time |
|
0.01h |
0~9999999.99h |
Comminications |
RS-485 (Optical Isolated) |
MODBUS RTU ProtocolIsolated1200 to 38400 baud rate |
|
|
|
|||||||| Click here for Input, Control Power and Output Specifications
Input |
Current Inputs (Each Channel) |
Nominal Current |
5A Secondary(1A Option) |
Full Scale |
120% of CT |
Burden |
0.2VA |
Overload |
2xCT for Continue20xCT for 1 Second |
Accuracy |
0.2% full scale |
Voltage Inputs (Each Channel) |
Nominal Full Scale |
400Vac L-N, 690Vac L-L |
Burden |
<0.2VA |
PT Prim./Sec. |
Direct or100~500,000:100~400 |
Input Range |
40~230V L-N,60~400V L-N |
Overload |
2xPT Continue, 2500V for 1 Minutes |
Accuracy |
0.2% full scale |
Digital Input (DI) |
Isolation Voltage: |
2500VAC rms Optical Isolated |
Input Type: |
Wet Contact |
Resistance: |
2K(Typical) |
Input Voltage: |
5~30Vdc |
Internal DI Power supply: |
15Vdc/60mA |
Close Contact Voltage: |
10Vdc |
SOE Resolution: |
1ms |
Max. Current |
20 mA |
Digital Output |
Relay Output (RO) |
Type: |
Mechanical Contact |
Max Voltage: |
250Vac or 30Vdc |
Configuration: |
A |
Isolate Voltage: |
2500Vac rms |
Output Mode: |
Latch or Momentary(50 to 6000ms) |
Max Current: |
3A |
Contact Material: |
Silver Alloy |
Digital Output |
Output Form: |
Photo-MOS, NO |
Optical Isolated: |
2500Vac rms |
Max. Negative Voltage: |
6Vdc |
Min. Positive Voltage: |
100Vdc |
Max Current: |
50 mA |
Pulse Output |
Parameters: |
kWh (Import, Export, Total, Net)kVarh (Inductive, Capacitive, Total, Net) |
Pulse Rate: |
1 to 6000, in step of 1(0.1kWh or 0.1kVarh) |
Pulse Width: |
20ms to 1000ms in step of 20ms |
Min Pulse Interval: |
20ms |
Alarm Output |
Alarm Items: |
All meteing parameters, Total: 242 |
Time Limit: |
0 to 76500ms in steps of 300ms |
Alarm Output: |
DO or RO |
|
|
|||||||| Click here for Operating Specifications and Size
Operating Environment |
General |
Operation Temp. |
- 25ºC to 70ºC |
Storage Temp. |
- 40ºC to 85ºC |
Relative Humidity |
95% non-condensing |
Power Supply |
Input: |
100V~240Vac 50/60Hz100V~300Vdc(24 or 48Vdc Option) |
Maximum power |
4W |
Dimensions |
Size |
96 x 96 x 51 (90 x 90 Cutout) |
|
|
|
|
|
|
Specifications |
|
|