- Horizontal
or vertical pipe mounting
-
Dust-ignition
proof
-
Highly
reliable
|
|
|
| |
| |
|
|
|
| |
|
|
The Model MLA and MLD field mounted remote indicators receive DC voltage or current signal inputs from electronic Transmitters and indicate process measurement values. They are available with Analog or Digital displays. Both accept 4-20 mA DC input. The remote indicator MLA also accepts 10-50Ma DC and 1-5 VDC. Mounting options are Horizontal or Vertical Pipe mounting, and wall mounting.
Our standard scale for MLA is black background, white numerals and letters, 50 divisions, 0-100%. For MLD, our standard display is 0-100.0%.
Loop powered indicators are commonly used to display process information that is being transmitted to a control room or control system. The display is either analog with pointer and scale or a digital LCD. Their purpose is to provide easy-to-read process values for maintenance or troubleshooting the control system.
These field mounted indicators receive DC voltage or current signal inputs from electronic Transmitters and indicate process measurement values. They are available with Analog or Digital displays. Both accept 4-20 mA DC input. The MLA also accepts 10-50Ma DC and 1-5 VDC. Mounting options are Horizontal or Vertical Pipe mounting. |
|
|
| |
| |
|
|
| |
|
| |
|
| MLA Series |
| Input Resistance: |
< 6.5 ohm (MLA 4-20mA),
< 13.5 ohm (MLA 10-50mA),
~4K ohm (MLA 1-5V) |
| Voltage Drop: |
1.8V typ., 2V max. (MLD) |
| Scale: |
Black. Analog single graduations 0-
100% standard. |
| Accuracy: |
± 1.5% of full scale (MLA) |
| Operating Temperature Range: |
-20 to
60°C |
| Vibration: |
1G @ 10-150Hz |
| Insulation Resistance: |
Between input
terminals and case 100 Mohm at 500 V DC |
| Dielectric Strength: |
Between input
terminals and case:
1000 VAC for 1 minute. |
| Mounting: |
Nominal 2” (50mm) pipe mount
or surface. |
| Electrical Classification: |
NEMA4X, FM,
CSA, EXPLOSIONPROOF CL1, DIV1, GPS
A,B,C,D, DUST-IGNITIONPROOF CLII / III,
GPS E,F,G |
| Case and Cover: |
Die cast aluminum, baked polyurethane paint.
Dark green; NEMA 4X
|
| Electrical Connection: |
NPT |
| Weight: |
3.0 lbs |
| MLD Series |
| Voltage Drop: |
1.8V typ., 2V max. (MLD) |
| Scale: |
Digital 0-100.0% w/decimal
standard. |
| Accuracy: |
± 0.05% of full scale (1999) +1 digit |
| Operating Temperature Range: |
0 to 60°C |
| Temperature drift: |
±0.3digit/°C |
| Vibration: |
3G @ 10-150Hz (MLD) |
| Insulation Resistance: |
Between input
terminals and case 100 Mohm at 500 V DC |
| Dielectric Strength: |
Between input
terminals and case:
1000 VAC for 1 minute. |
| Mounting: |
Nominal 2” (50mm) pipe mount
or surface. |
| Electrical Classification: |
NEMA4X, FM,
CSA, EXPLOSIONPROOF CL1, DIV1, GPS
A,B,C,D, DUST-IGNITIONPROOF CLII / III,
GPS E,F,G |
| Case and Cover: |
Die cast aluminum, baked polyurethane paint.
Dark green; NEMA 4X |
| Electrical Connection: |
NPT |
| Weight: |
2.7 lbs |
|
|
| |
| |
|
|
|
|
| |
| |
General Specifcations |
|
|
|
|
|