- Accuracy: ±2%
- ± 3% AC - rectifier type (60 Hz sine wave)
- Full range of inputs
- Tracking: ± 1 1/2% DC
- Repeatability: ± 0.5% DC and rectifier type
- Orientation: Horizintal, Vertical or specified mounting angle
- Slim Compact design provides the answer to "space" problems
- They can stand alone or be stacked in space-saving clusters
- UL, CSA models avaliable
|
|
|
| |
| |
|
|
|
| |
|
|
The edgewise family of panel meter products were designed to handle applications where panel space is at a premium.The 280 edgewise series may be mounted horizontally or vertically and meet ANSI C39.1. The Yokogawa line of edgewise meters are accurate to within ±2% of full scale in DC and ±3% for AC and come in a variety of sizes and ratings.
The thin element design provides the maximum performance in the smallest of spaces. Available in 1 1/2" to 3 1/2" sizes for vertical or horizontal mounting. They can stand alone or be stacked in space-saving clusters. Built-in magnetic shielding prevents interference among meters and removes the burden of special calibration. |
|
|
| |
| |
|
|
| |
|
| |
|
| Display |
| Scaling: |
Customized to any scaling desired, from linear to specialized Cos Ø, square root distributions, with color applications for visual emphasis and to any desired engineering units. |
| Specific Accuracies |
| Basic Accuracy: |
±2.0% of full scale basic accuracy class. |
| Rectifier Type Meters: |
±3% of full scale basic accuracy class. |
| Zero Suppressed Meters: |
Errors at 20% suppression = ±3%
of end-scale |
| Higher Accuracy: |
1% of Full scale or better |
| |
| Position of use: |
Horizontal (scale) standard, Vertical
or to specified angle or position |
| Full scale deflection angle: |
53 ° |
| Full scale length: |
Size |
Arc Length |
| 11⁄2” |
1.93" |
| 21⁄2” |
1.93" |
| 31⁄2” |
2.70” |
| Movement: |
Taut Band |
| The absence of friction
resulting from this permits greater sensitivities
and provides more rugged meters.Common
failures of conventional meters subjected to
shock testing are cracked jewels and/or
blunted pivots. |
| Pointer: |
Standard Red |
| Case and Cover: |
Clear plastic |
| Dielectric (Hi-pot): |
1500 VRMS for 1-1/2” and 2-1/2” sizes. 2600 VRMS for 3-1/2” size. |
| Overload rating: |
DC Voltmeters — 20% momentary and sustained; DC ammeters (momentary) — 10 times the rated current for 10 consecutive intervals of .5 second with 1 minute intervals between successive applications; DC ammeters (sustained) — 20% for 6 hours |
| Overshoot: |
25% (max.) for 1-1/2” size, 40% (max.) for 2-1/2” and 3-1/2” sizes |
| Response time: |
3 seconds max for µA meters
2 seconds (max.) for mA, A, mV, & V meters |
| General: |
| Operating Temp.: |
0 to 40°C (32 to 104°F) |
| Storage Temp: |
-10 to 50°C (14 to 50°F) |
| Relative Humidity: |
95% (non condensing) |
| Bezel and Mounting Hardware: |
Included with meter |
| Dimensions |
| 1 1/2" Meters |
Download PDF File |
| 2 1/2" Meters |
Download PDF File |
| 3 1/2" Meters |
Download PDF File |
|
|
| |
| |
|
|
|
|
| |
| |
General Specifcations |
|
|
|
|
|