Spacer Home Contact_us ob Opportunities ISO_Registration Privacy_Statement
 
Caption_Header
Yokogawa
103 Series (AB-40)
4 1/2" Elapsed Time Meters
 
previous URL Next URL
< Links >
 
 
 
cart   Order YOKOGAWA TMI Products on-line
 
green_line
 
 

Yokogawa 103 Elapsed Time Meters

 Characteristics:

green_line
 
  • Models are available with time range of 0 to 99,999.9 hours in reset and non-reset configuations.
  • Materials: Polycarbonate cover and zinc-coated steel case
  • Presentation: Six digit counter with 5/32" high digits.
 
 
  Product Description:
space
green_line
 

 

Time-proven 240 elapsed time meter in a 4.33" square weather-resistant case. It is designed for use with other switchboard instruments on electrical switchgear and control panels. It is UL/CSA recognized under file E 44857 and meets ANSI C39.1 specifications for shock and vibration. Accuracy of these AC hour meters matches the frequency control of the power system

 
 
  Specifications :
 
green_line
 
space
 
Display: 6-digit counter in 5⁄32” high hours and tenths of hours or minutes and tenths of minutes.
Basic Accuracy: Matches frequency control of power system.
 
Vibration Shock: Meets ANSI Specification C39.1
Safety: Type 240 elapsed-time meters are recognized under the Component Program of Underwriters’ Laboratories. (UL File #E44857) & CSA
Input Range: All Type 240 models available to operate on 120 or 208/240 or 480 volts AC, 50 or 60 Hertz.
Sealing: All non-reset Type 240 models are weather resistant. Sealed window and nothrough screw holes for flange or back-ofpanel mounting protect motor, counter, and gearing from rain or panel wash-down.
Case: All AB/DB switchboard instruments have drawn steel case with zinc chromate coating except AB/DB40 plastic case version which is ABS plastic.
Cover: Gasketted cover to prevent contaminant ingress, polycarbonate-UL94V-0 cover and window.
Terminal plate: phenol resin material.
Mounting studs: 1/4” x 28 thread.
Terminal studs: 10-32 thread.
Dielectric (Hi-pot): 1500 VRMS for 1-1/2” and 2-1/2” sizes. 2600 VRMS for 3-1/2” size.
Insulation Level: 1800 VRMS Hi-pot.
Overload rating:

Operating at 120, 208, 240 or 480 volts AC, will pass Hi-pot of 2000 VRMS for one minute.

Burden: 3 Watts typical.
Motor: Telechron, Model S-1.
General:
Operating Temp.: 0 to 40°C (32 to 104°F)
Storage Temp: -10 to 50°C (14 to 50°F)
Relative Humidity: 95% (non condensing)
Mounting Hardware: Included with meter
 
 