Yokogawa 103 Dual-Vue Switchboard Meters

 Characteristics:

green_line
 
  • 250 degree scale deflection
  • LED illuminated versions available in Red, White
  • Built-in Transducer for scaling linearization
  • Linear scaling allows product flexibility
  • Meters accurate to within ±1% of full scale
  • Available in AC/DC Amps & Volts, AC Watts/VARS/Power Factor/Frequency/Synchroscope, RTD Temperature
  • Tracking: ± 1 1/2% DC; ± 2% AC ; vertical mounting
  • Repeatability: ± 0.5% DC and rectifier type
  • Water tight construction
  • Shock resistant Pivot and jewel movement
  • UL, CSA and IP54 splash proof models avaliable
  • In Accordance to ANSI C39.1
 
 
  Product Description:
space
green_line
 

 

Dual-Vue switchboard meters are combination Digital/Analog indicating instruments. They can be configured to accept ACV, ACA, DCV, or DCA input. Both the digital and analog displays can be modified to represent virtually any scaling or engineering units as required. The unit is contained in a 4 1/4” Switchboard housing. It utilizes a taut band moving element and a 0.56”, 3 1/2 digit display for indication (+ or – 1999 counts).

 
 
  Specifications :
 
green_line
 
space
Digital Portion
Digital Meter: Digital: 3 1/2 digit, 7 segment display 0.56” (14.2mm) digit height. Red, blue or green LED. Negative Polarity indicator. Selectable decimal point settings. Update rate is 2.5 times/second. Response time less than 1 second (0-90%)
Accuray: AC +/-0.1% of reading +/-3 counts.
DC +/- 2 counts
Temperature Coefficient: 200ppm/°C of full scale for digital display. Less than 1% additional analog display error over operating temperature range.
Long Term Stability: +/-2 counts (digital), +/-0.8% (analog)
Warm Up time: 10 minutes
Voltage: 120V +/-15% standard ; optional 240V +/15%
Frequency: 50/60Hz +/- 2Hz (48Hzto 62Hz)Burden:<3.5VA
Analog Portion
Scaling: Customized to any scaling desired, from linear to specialized Cos Ø, square root distributions, with color applications for visual emphasis and to any desired engineering unit.
Specific Accuracies
Basic Accuracy: ±1.0% of full scale basic accuracy class.
Rectifier Type Meters: ±1.5% @ 25°C calibrated to sine wave.
Expanded Scale Voltmeters: 0.3% of mid-scale
Frequency Meters: ± .15Hz @45-55Hz and 55-65Hz, ±0.093Hz @ 58-62Hz, ±1.5Hz @350-450Hz
 
Position of use: Vertical (scale) standard
or to specified angle or position
Full scale deflection angle: 220°
Full scale length: 6.9 inches.
Scale plate:

Single, flat scale

Movement: Proven, shock resistant Taut Band
Case: All AB/DB switchboard instruments have drawn steel case with zinc chromate coating except AB/DB40 plastic case version which is ABS plastic.
Cover: Gasketted cover to prevent contaminant ingress, polycarbonate-UL94V-0 cover and window.
Terminal plate: phenol resin material.
Mounting studs: 1/4” x 28 thread.
Terminal studs: 10-32 thread.
Dielectric level: 2300VAC for 1 minute between the electrical circuit and mounting studs.
Overload rating: Voltmeter and potential coils-1.2 x rating (continuous). AC Ammeters- 2 x rating (continuous), and 10 x rating for one second. Current coils (other than ammeters) 1.5 x rating (continuous), and 10 x rating for one second.
Response time: Approximately 2.5 seconds
General:
Operating Temp.: 0 to 40°C (32 to 104°F)
Storage Temp: -10 to 50°C (14 to 50°F)
Extreme temperature range:

-20°C to 65°C (-4 to 149°F)
Tropicalized or IP54 sealed units available

Relative Humidity: 95% (non condensing)
Case Dimensions:
Meter Face: 4.33" X 4.33"
Case Depth:

4.10"

Case Diameter: 3.97"
Cut out Diameter 4.030"
Studs 1.688" from mid-line (Hor. & Vert.)
3.375" between studs (Hor. & Vert.)
 
 