- Selectable 4,000 and 40,000 count display
- Dual display, Digital and Analog
- Analog bar graph updates 128 times every second
- True rms (a.c. + d.c.) and average responding models
- Basic accuracy from 0.08%
|
|
|
|
 |
| |
|
|
| |
|
The M8000 Series of advanced analog/digital multimeters from Megger use the latest microprocessor technology to provide the most comprehensive measuring ranges and features in a hand held instrument.
The M8000 models provide more advanced features for applications requiring more extensive measuring capabilities. The M8037 is the is the top-of-the-line instrument. It measures TRMS dc and ac which will allow more accurate measurements of various waveforms: sine, sawtooth, square, pulse trains, triangle, spikes, etc., as well as distorted waveforms with the presence of harmonics. The M8037 also features a backlight display for easier reading in poorly illuminated areas. Both the M8035 and M8037 have basic accuracies of 0.08%, dual displays and the choice of operation in the manual or autoranging mode.
Capacitance, frequency, conductance and diode test facilities are included as standard features, plus for more advanced measurement applications the ability to record, store, sort and compare results is also provided. |
|
| |
| |
|
|
|
| |
| |
- 4,000/40,000 Counts
To ensure maximum speed, accuracy and resolution, the
fast 33⁄4 digit 4,000 count display updates 5 times per
second (nominally). The user-selected 10 x higher
resolution mode 43⁄4 digit count display updates
approximately every 3⁄4 s, and is available in most
measurement functions.
- analog Bar Graph
The 43 segment analog bar graph updates 128 times/sec
in d.c. voltage and resistance functions enabling the user
to easily detect faulty contacts, identify potentiometer
clicks and indicate signal spikes during adjustments. In
other modes and other functions the bar graph updates 20
times/sec showing excellent trending characteristics.
- Dual Display
Innovative LCD and microprocessor technology has been
utilised to provide dual displays in various modes. Using
this feature one can simultaneously display a.c. volts +
frequency, a.c. amps + frequency, conductance +
resistance, duty cycle + frequency, dbm + frequency and
values + events.
- Fast 150 μs Audible Continuity Test
The audible continuity test is a quick go/no-go test that
distinguishes between an open and a closed circuit. The
meter will give a continuous beep tone when the input
resistance drops below 10 ½. This is useful for checking
wiring connections and operation of switches.
- Relative Functions
There are three different relative modes to choose from;
Relative Zero, Relative Percentage and Relative per Unit.
In Relative Zero mode the user is allowed to offset the
meter measurements with a relative reference value,
therefore subtracting this reference from any further
measurement. In Relative Percentage change mode the bar
graph automatically indicates ±200% or ±20% for full scale
changes with respect to the Relative Reference value
which becomes centre zero point. This simplifies zero,
peaking, nulling measurements and is excellent for fine
adjustments. The final relative range is Relative per Unit
which shows the ratio of measuring values to the relative
base value. For example measuring the parallel
capacitance of co-axial cable or parallel wire in
conjunction with the Relative per Unit mode, helps
estimate the total cable length or pinpoint cable
breakdown locations.
- Record Max, Min, Max-Min and Average
Using the Record you can easily track intermittent signals,
capture turn-on/turn-off surges and monitor line voltage
changes over a much wider dynamic range with the
highest resolution. The faster the sampling speed, the
more accurate the measurement of surges, spikes and sags
will be. The true average continually calculates all
readings taken over time.
- Data Store & Recall (MEM)
This feature stores the whole display data in memory for
later recall. The memory will remain even in auto-poweroff
mode and can also be recalled at any time, even while
being operated in another measuring function.
|
|
| |
| |
|
|
|
| |
| |
|
8037 |
8035 |
| A.C. Conversion Type: |
True RMS |
Average responding |
| Backlit LCD: |
Yes |
NA |
| Crest/Peak: |
0,8 ms response, Max, Min
Max-Min |
0,8 ms response, Max, Min Max-Min |
| Sort: |
Auto-ranging, Max, Min, |
| Input Warning: |
Audible & Visible |
| Total Functions: |
55 Ranges |
| DCV |
400 mV to 1 kV
in 6 ranges |
| Best Resolution: |
1μV |
| Basic Accuracy: |
± 0,08% ± 1 digit
(0,5% ±6d on 40,00 mV)
|
| NMRR @ 50/60 Hz: |
> 60 dB |
| CMRR @ DC, 50/60 Hz: |
> 120 dB @ d.c. & 50/60 Hz |
| ACV |
400 mV to 750 V
in 5 ranges |
| Best Resolution: |
10 μV |
| Basic Accuracy: |
±0,5% ±3 digits
50-60 Hz |
| Basic Bandwidth: |
40 Hz - 20 kHz |
| CMRR @ DC, 50/60 Hz: |
> 60 dB |
| DCA/ACA |
4000 μA to 10 A
in 6 ranges
|
| Best Resolution: |
0,01 μA
|
| Basic Accuracy (DC): |
from ±0,2% ±2 digits to 1% ± 4 digits |
| Resistance |
40 to 40 M Ω in 7 ranges |
| Best Resolution: |
0,001 Ω |
| Basic Accuracy: |
<400 kΩ ±0,15% ±2 dig., 40 MΩ 1.5% ±5 dig |
| Conductance |
400 nS in 1 range
|
| Best Resolution: |
0,1 nS
|
| Basic Accuracy: |
±0,7% ±5 digits |
| Capacitance |
4 nF to 40 mF in 8 ranges |
| Best Resolution: |
1 pF |
| Basic Accuracy: |
40 nF - 4 μF: 0,8% ±5 dig. <40 nF, >4 μF ±4% |
| Frequency |
100 Hz to 4 MHz in 6 ranges |
| Best Resolution: |
0,001 Hz |
| Basic Accuracy: |
±0,002% ±3 digits |
| Duty Cycle |
100% in 1 range |
NA |
| Best Resolution: |
0,1% |
NA |
| Basic Accuracy: |
±0,5 digits/kHz
±2 digits |
NA |
| (AC+DC)V |
4 V to 750 V in 4 ranges |
NA |
| Best Resolution: |
0,1 mV |
NA |
| Basic Accuracy: |
±0,8% ±8 digits
(40 Hz - 20 kHz) |
NA |
| dBm |
-60,7 dBm to 81,4 dBm Automatic with 20 reference Ω |
NA |
| Best Resolution: |
0,01 dBm |
NA |
| Basic Accuracy: |
±0,25 dBm ±2 digits
@ 40 Hz to 20 kHz |
NA |
|
|
| |
| |
|
|
|
|
| |
| |
 |
|
|
|
|
 |
 |
|
|
|
|
Display
4,000 count (updated every 0,2s)
40,000 count (updated every 0,8s)
Bargraph (updated every 8 ms)
Dual display:
10,000 counts
Features
Data Hold
Data record: 50 ms response, autorange max, min, max-min span,
average
Store and Recall:
Relative zeroing with centre-zero auto-zoom bargraph
relative units
relative % change
relative per unit change
Quick Continuity test:
response <150 μs, turn on <10 Ω, turnoff >60 Ω
Line Frequency filter:
60/50 Hz switchable
Diode Test:
4,000 count V range, test current (typical) 0,8 mA open circuit<3,5 V d.
Automatic PowerOff:
5 minutes (default)/5 sec/off
Safety
rated to IEC 1010 Cat III 600 V, Cat II 1000 V
EMC
In accordance with IEC61326 including amendment No.1
|
|
| |
 |
|
|