- Storage of test results
- Recall of test results to instrument display
- Direct serial printer output via RS232 port
- Connect to IBM compatible PC for storage of results
- Ramp Test for measuring RCD actual trip currents
- Variable RCD test current for programmable devices
- Designed and manufactured in accordance with International Safety Standards
- Insulation tests at 250 V, 500 V & 1000 V with 1 mA
output
- Continuity tests with 200 mA short circuit capability
- Phase-Phase, Phase-Neutral, Phase-Earth Loop Tests
- High current Loop Testing with 0,01 Ω resolution
- Prospective Earth Fault and Short Circuit Current
Tests in accordance with International Standards and
National Wiring Regulations including BS7671 (16th edition
wiring regulations) and Euro Standard EN61557.
Test lead resistances can be nulled and a continuity buzzer
is incorporated for rapid identification of open and short
circuits. Settable automatic polarity reversal and result
averaging.
Loop tests are performed to a resolution of 0,01 Ω with
direct display of PEFC and PSCC.
A unique low current Loop Test with 0,1Ω resolution for
testing circuits protected by an RCD rated at 30 mA or
above, without tripping the RCD, including the newer
electronic ones.
Auto-ranging earth resistance function enables
measurement of earth electrode resistance on TT systems.
Verification of the correct operation of RCDs rated
between 10 mA and 1000 mA with trip timing up to
2000 ms. A ramp test indicate actual trip current to aid in
fault diagnosis and variable test current function enables the testing of programmable and specialist devices.
Upon connection to the mains supply the polarity and voltage are displayed to show correct wiring of the socket under
test and warn of live voltages. Supply frequency is indicated at the touch of a button.
Approximately 750 different results may be saved into internal memory for use later on.
Stored results may be recalled to the CM500 display to enable reviewing and facilitate the manual recording and completion of test reports and certificates.
Test results may be printed directly on site by simply connecting an appropriate serial printer to the RS232 port.
A standard RS232 serial port enables test results to be downloaded to a PC for later use. The ultimate solution is provided
with the use of PowerSuite™ for Windows™.
Meets or exceeds the requirements of EN61010-1 Category III 480 V (max) phase-phase. |