Megger ®
BM80/2 and BM81/2 Series
Multi-Voltage Insulation & Continuity Testers
 
previous URL Next URL
< Links >
 
 
 
Megger BM80/2 Insulation Tester
 
  Characteristics:  
 
 
  • Analog and Digital display of data
  • Fully complies with the requirements of BS 7671, HD 384 and IEC 364
  • Multiple insulation test voltages from 50 V to 1000 V d.c. (according to model)
  • Remote control switched probe option
  • Optional RS232 port
  • Optional current clamp accessory
  • Waterproof and dustproof to IP54
 
 
  Product Description:  
 

 

 

space

The MEGGER BM80/2 Series are multivoltage insulation and continuity testers offering advanced performance, specification and features, and simplicity of use. They have insulation test voltages from 50 V to 1000 V d.c., (500 V max. on BM81/2.) The comprehensive specification is achieved using the latest electronic design and technology.

 
 
  Applications  
 

ELECTRICAL CONTRACTORS

  • These insulation testers are designed for flexibility and versatility, they have a wide variety of applications, ideal for testing electrical installations to the British and International Wiring Regulations. Each instrument in the series conforms to the requirements of Table 71 A in BS 7671, and to VDE 0413 parts 1 and 4, HD384 and IEC364.
  • The BM80/2 series can be used in both the domestic and industrial contracting environments. Test voltages of 250 V, 500 V and 1000 VDC are available. A 250 V insulation test voltage is necessary to test low voltage circuits supplied by an isolating transformer. 500 VDC is the most commonly required voltage, since it is used to test all circuits except low voltage circuits with a nominal voltage up to and including 500 V. The 1000 VDC test voltage is used on circuits with a nominal voltage greater than 500 V and less than 1000 VDC ring final circuit conductors, and the polarity of the conductors.
  • The BM80/2 can also be used for insulation and continuity tests on transformers, motors, generators, domestic appliances, power tools, such as electric drills, and many other pieces of electrical equipment. On high energy systems it is recommended that test leads with fused prods are used when measuring voltage.
 
 
  Specifications:  
space
 
Insulation Ranges
Test Voltages : 50 V, 100 V, 250 V, 500 V and 1000 V
(1000 V not available on BM81/2.)
Measuring Range:
1000 V range: 0–200 GΩ
500 V range: 0–100 GΩ
250 V range: 0–50 GΩ
100V range: 0–20 GΩ
50 V 0–10 GΩ
Test voltage accuracy: +15% maximum on open circuit
Test Current on load:

1 mA minimum at the minimum pass values of insulation specified in BS 7671 (formerly the 16th Edition IEE Wiring Regulations)on the 250V, 500 V and 1000 V ranges.
50 V range: 0,2 mA at 250 kΩ
100 V range: 0,4 mA at 250 kΩ

Accuracy:
1000 V ±2% ±2 digits ±0.4% per GΩ
500 V ±2% ±2 digits ±0.4% per GΩ
250 V

±2% ±2 digits ±0.8% per GΩ

100V ±2% ±2 digits ±2% per GΩ
50 V ±2% ±2 digits ±4% per GΩ
Continuity
Measuring Range: 0,01 Ω to 99,9 Ω (0-50 Ω on analog scale)
Accuracy:
±2% ±2 digits
Open circuit voltage:

5 V ±1V

Test current: 205 mA, ± 5 mA
Continuity Buzzer Operates at less than 5 Ω approx.
Resistance
Measuring Range: 0,1 - 100 kΩ
(0 - 10 MΩ on analog scale)
Accuracy: ± 3% ± 2 digits
Open circuit voltage:

5 V ±1V

Short circuit current 20 μA, ±5 μA
Voltage
Measuring Range: 0 to 600 V AC/DC, 0 to 50 V AC/DC,
Accuracy: <450 V a.c. (50/60 Hz) and d.c.
±1%, ±2 digits
>450 V a.c. (50/60 Hz) and d.c.
±2%, ±2 digits
<450 V a.c. 400 Hz: ±5%, ±2 digits
1,0-50,0 V Range a.c./d.c.
±2%, ±3 digits
Default Voltmeter
The default voltmeter operates when an external voltage >25 V a.c. or d.c. is detected on any range except OFF and . If this voltage exceeds 55 V then insulation testing will be inhibited. Reverse polarity d.c. will cause ‘-d.c.’ to appear on the DISPLAY.
Auto Shut off
The instrument auto shut off operates 5 minutes after the start of a test, on all ranges, except the insulation ranges where it operates after 12 minutes. This can be adjusted to 60 minutes for the voltage, continuity and KΩ ranges. Selecting an insulation range or off
Power
Battery Type:: 6 x 1,5 V Alkaline cells IEC LR6 type
Battery Life: Typically 3000, 5 second 1 kV tests
Safety
The instruments meet the requirements for double insulation to IEC 1010-1 (1995), EN61010-1 (1995) to Category III, 300 V phase to earth (ground) and 440 V phase to phase. Over voltage measuring facilities exist to indicate capacitive discharges. FUSE PROTECTED TO 440 V.
 
 
  Downloads:  
space
 
  pdf_pic Downloads: General Specifications  
space space
base

GENERAL SPECIFICATION
Operating Range
-20 - +40 °C
Operating Humidity
90% R.H. at 40 °C max.
Storage Range
-25 - +65 °C
Environmental Protection IP54

FUSE
Type
500 mA (F) 440 V, 32 x 6 mm Ceramic HBC 10 kA minimum.
Indication of a ruptured fuse is provided by the symbol .

SAFETY
The instruments meet the requirements for double insulation to IEC 1010-1 (1995), EN61010-1 (1995) to Category III, 300 V phase to earth (ground) and 440 V phase to phase. Over voltage measuring facilities exist to indicate capacitive discharges.

FUSE PROTECTED TO 440 V.

INSTALLATION CATEGORIES
Category III: Fixed wiring and installations within a building.

AUTOMATIC DISCHARGE
When the test button is released after an insulation test the item under test will be discharged automatically. Any voltage present will be indicated on the display so that the discharge can be monitored.

POWER SUPPLY
Battery Type
6 x 1,5 V cells IEC LR6 type only.
Battery Life
3000, 5 second operations, at 1 kV worst case
Weight
625g (1,377 lbs approx.)
Dimensions
220 x 92 x 55 mm
(5,5 in x 2,33 x 2,16 in approx.)
E.M.C
The instrument meets EN50081-1 and
EN50082-1.)

 
 