Model DCM2031, DCM2033, DCM2039,
Digital Clamp-on Meters
 
previous URL Next URL
< Links >
 
 
 
  Megger DCM2000 Clamp Meters  
 
  Characteristics:  
 
 
  • Excellent Price Performance
  • Three Models 400 A, 600 A and 1000 A
  • Drop Proof
  • EMC & IEC1010 Compliance
  • Multi-meter clamp accessory to 400A ac
  • Clamp-on multimeter: measures to 600A ac, 600V ac and 40 kilohm
  • High current ac/dc clampmeter to 7000A
 
 
  Product Description:  
 

 

 

 

The DCM clampmeters are the ideal instruments for use in the installation, maintenance, monitoring or checking of electrical systems and equipment. There are three different current clamps in the DCM range covering many applications.

The series starts with a plugin unit for basic a.c. current measurements made in conjunction with a multimeter, a volt plus current unit where the user needs the flexibility of being able to make voltage measurements as well as current measurements and a high current a.c./d.c. unit.

These current clamps can be used to simplify current measurements, ideal for commissioning and maintenance work and for routine testing or fault finding in electrical machinery, plant equipment or on cable installations. Typical applications include measuring current when balancing the load on three phase supplies or checking feeder lines in the electrical supply industry.

 
 
  Ranges and Accuracies:  
 
AC Current
DCM2031
DCM2033
DCM2039
Ranges 400 A 400 A, 600 A 400 A, 1000 A
Resolution 1m V/A 0,1 A  
Accuracy ±(1,9% +0,5A), 50 - 60H
±(3,9% +1A), 40 - 400H
50Hz - 60H
±(1,9% rdg +5d),
0 - 400 A
±(2,9% rdg +5d),
400 - 600 A
40Hz - 400Hz
±(1,9% rdg +8d),
0 - 40 A
±(1,9% rdg +7d),
40 - 400 A
±(2,9% rdg +5d),
400 - 1000 A
Conversion Type   Average sensing RMS indicating Average sensing RMS indicating
AC Voltage
DCM2031
DCM2033
DCM2039
Ranges   400 V, 600 V
 
Resolution   0,1 V in the 400 V  
Accuracy   ±(1,2% rdg + 5d),
40Hz - 500Hz
 
Input Impedance   10 MΩ<100pF  
Protection   a.c. 850 V rms  
Conversion Type   Average sensing RMS indicating  
Resistance
DCM2031
DCM2033
DCM2039
Ranges   4 kΩ, 40 kΩ  
Resolution   1Ω in the 4kΩ range  
Accuracy   ±(2% rdg +9d)  
Overload Protection   500 V rms  
DC Current
DCM2031
DCM2033
DCM2039
Ranges     400 A, 1000 A
Resolution     0,1 A
Accuracy     ±(2,9% rdg +8d),
0 - 40 A
±(1,9% rdg +4d),
40 - 400 A
±(2,9% rdg +5d),
400 - 1000 A
Frequency
DCM2031
DCM2033
DCM2039
Ranges     20 Hz to 10 kHz
Accuracy     ±(0,5% rdg+ 3d)
Frequency
DCM2031
DCM2033
DCM2039
Threshold   <200Ω approximate  
Indicator   2 kHz tone buzzer  
 
  Product Specifications:  
 
Parameters
DCM2031
DCM2033
DCM2039
Display (LCD) none 4000 count 4000 count
Measuring Rate continuous 4 T/sec 2 T/sec
Position Error ±1%    
Output Voltage a.c. 1 mV/A Per 1 A - -
Type of Sensing current transformer current transformer Hall Effect (for a.c. & d.c.)
Overrange indication   “OL” “OL”
Low Battery Indicator   + - + -
Auto Power   30 min. non-use 30 min. non-use
Operating Temperature   0°C ~ 45°C, <75% R.H.  
Storage Temperature   -20°C ~ 60°C,<80% R.H.  
Temperature Coefficient   0,2 x (spec. Acc’y)/*C,<18*C or >28*C  
Shock Proof   4 feet drop  
Max. Conductor size dia.29 mm dia.40mm dia.51 mm
Maximum Jaw Opening 30 mm 42mm 53 mm
Maximum Busbar Size     24 x 60 mm
Power Requirement   9 V PP3 (IEC 6LR61) 9 V PP3 (IEC 6LR61)
Battery Life (Alkaline)   200 hrs 40 hrs
Size W x L x D in mm 72 x 148 x 36, w/o cable 88 x 215 x 36 106 x 240 x 40
Weight 250 g 320 g 420 g
 
  Downloads:  
space
 
  pdf_pic Downloads: General Specifications  
base

APPLICATIONS

These current clamps can be used to simplify current measurements since there is no need to switch off or break the circuit carrying the current. Instead, the clamp jaws surround the conductor while it remains energised. This makes the units ideal for commissioning and maintenance work and for routine testing or fault finding in electrical machinery, plant equipment or on cable installations. Typical applications include measuring current when balancing the load on three phase supplies or checking feeder lines in the electrical supply industry.

Safety
The tactile barrier indicates to the operator a safe working distance for his hand to be from live uninsulated conductors, providing added confidence when making measurements in hazardous voltage areas.

 