- AC. and DC Amperes, Ohms, Diode & Continuity
- IEC1010 & EMC Compliance
- RMS measurement
- Auto-ranging & Auto-zeroing
- Excellent accuracy
- Display – Hold and Max
- analog outputs
|
|
| |
| |
|
|
| |
|
The DCM R series of digital clamp
meters have a four digit L.C.D. and
are available in different versions for
maximum currents of 200 A, 1000 A
and 2000 A. They feature autoranging
and auto-zeroing and can
measure a.c., d.c., pulsed and mixed
currents. Additional functions include
the measurement of voltage,
resistance, continuity and a diode test.
The overall accuracy of 1,3% of the
measured value has been achieved by
utilising the latest microprocessor
technology, plus the use of a true
RMS measuring technique. This
accuracy even applies when
harmonics or complex waveforms are
present.
The clampmeters have additional
ranges of 400 V, 600 V, 400 ½, 4 k½ and allow diode tests as well as
continuity tests with an integrated
buzzer. Simply by pushing a button, it
is possible to freeze the last value
measured or to display the peak
value on the four digit 12 mm high
liquid crystal display. The analog
outputs of this DCM series can be
connected to an oscilloscope, chart
recorder, datalogger or other
measuring/recording equipment. A
true RMS output is also available.
The traditional measuring method for
taking current measurements by
inserting a shunt resistor or a
current transformer has inherent
disadvantages, such as the necessity
to break the circuit conductor. The
modern, competitively priced Hall
effect DCM R series Clamp-on
multimeters offer the user many
advantages including the
measurement of d.c. currents and
non-sinusoidal waveforms. |
|
| |
| |
|
|
|
| |
| Voltage Measurement |
|
| Methods of measurement |
AC True RMS or DC |
| Maximum overload |
1000 V |
| Accuracy |
±1% of reading ±3 digits |
| Resolution |
100 mV (400 V range) |
| Crest Factor |
6 for V < 1000 V peak |
| Input Impedance |
1 MΩ |
| Resistance, Continuity and Diode Testing |
| Ω ranges (auto-ranging) |
400Ω , 4 kΩ |
| Ω resolution |
0,1Ω (400 Ω range) |
| Ω accuracy |
±1% of reading ±3 digits |
| Continuity sounder Toggled |
on & off by button |
| (Ω range only) |
Sounds when resistance <50 Ω |
| Input protection, Ω & diode test |
To 600 V, DC or sinewave |
| Diode test |
3,2 V max. open Reads forward - biased diode |
| circuit, 0,3 mA short circuit |
Voltage to 2000 mV |
| Diode test |
accuracy ±1% of reading ±2 digit |
| Frequency Response (Measurements and analog output) |
| AC only True RMS V & A |
15 Hz to 1 kHz |
| DC True RMS A |
DC. +15 Hz to 1 kHz |
| DC V and A |
DC only |
| Display |
|
| Size and type |
40000 count LCD
12 mm (0,5 in) characters |
| Status indication |
Low Battery, Data Hold
PK (MAX hold), a.c., d.c., Diode
Test, Ω, Continuity |
| Refresh rate |
3 times per second |
| General |
|
| Battery type |
9 V alkaline: MN1604, PP3,
IEC 6LR61 or equivalent |
| Battery life |
Typically 40 hours |
| Dimensions |
(H x W x D) 251 x 98 x 53 mm
(9,88 x 3,86 x 2,05 ins.) |
| Weight |
500 gm (1,1 lbs)
|
| Jaw capacity |
1 x 50 mm (2,0 in) dia. cable Ω
2 x 30 mm (1,2 in) dia. cables |
|
| |
| |
|
|
|
| |
Models |
DCM24R |
DCM104R |
DCM204R |
| Ranges |
40 A, 200 A |
400 A, 1000 V |
400 A, 2000 A |
| Measurement methods |
AC or DC. True RMS, or DC only |
| Resolution |
10 mA
(40 A range )
100 m A
(200 A range) |
100 mA
(400 A range)
1 A (1000 A range) |
100 mA
(400 A range)
1 A (2000 A range) |
| Accuracy |
±1,3% of reading ±3 digital |
| Maximum measureable load |
200 A d.c. or a.c. peak |
1000 A d.c. or a.c. peak |
2000 A d.c. or a.c. peak |
| Crest Factor |
6 maximum for True RMS measurements |
| Maximum overload |
10 000 A |
analog Output (2)
Switcheable Instantaneous or RMS (100 ms) output |
5 mV/A |
1 mV/A |
0,5 mV/A |
| analog output accuracy |
|
±1,3% of reading ±1 mV |
|
|
| |
| |
|
|
|
|
| |
| |
 |
|
|