Megger TDR1000/2 Time Domain Reflectometer

Characteristics:

  • Simple operation
  • Fast fault find facility
  • Adjustable display contrast
  • Resolution to 0.1 m
  • TX Null transmission pulse nulling
  • User selectable output impedance 25 Ω, 50 Ω, 75 Ω and 100 Ω
  • Adjustable cable impedance
  • Range, gain and cursor automatically adjusted to find event on press of a button
  • Display distance in metres or feet
  • Uses six AA (6LR61) primary cells
  • No blocking filter required
  • IP54 rating
 
 
space
  Product Description:  
 

 

 

 

The TDR1000/2 is a hand held, compact Time Domain Reflectometer for locating faults on metallic cables. It has a minimum resolution of 0.1m/0.3ft and a 3km/9kft maximum range depending on Velocity factor selected and cable type.

Four output impedances are available (25, 50, 75, and 100 ohms) and a velocity factor between 0.2 and 0.99 will meet any cable test requirements

  • The MEGGER TDR1000 features all the benefits of a simple low cost hand held TDR
  • Ease of use is a key feature and with a simple ‘one Key one function’ approach.
  • Automatic Event Location further simplifies operation producing a reduction in training time and product familiarization

Enhanced key pad navigation
Control of the TDR1000/2 has been simplified with each key having a dedicated function, such as cursor left and right, Velocity factor, range etc. Training times are dramatically reduced, and with less chance of time consuming mistakes, productivity is improved.

TX Null
TX Null eliminates the ‘dead zone’ at the start of the displayed trace, normally obscured by the transmission pulse. By adjusting the TX Null control the user can see these ‘near end’ faults clearly.

Fast Find key
Reduces the time taken to find major reflections on the cable. One press of the find key automatically adjusts the range and gain and positions the cursor to the major event on the cable within seconds, removing the need for the engineer to gradually scroll through the ranges looking for the fault or the end of cable reflection.

 
 
  General Specifications :  
 
space
   
Ranges: 10 m, 30 m, 100 m, 300 m, 1000 m, 3000 m
(30 ft, 100 ft, 300 ft, 1000 ft, 3000 ft, 10000 ft)
Accuracy: ±1% of range ± pixel at 0.67VF
[Note- The measurement accuracy is for the indicated cursor position only and is conditional on the velocity factor being correct.]
Resolution: 1% of range
Input Protection: This instrument complies with IEC61010-1 for connection to live systems up to 300 V CAT III. Fused leads must be used if the voltage between the terminals exceeds 300 V.± 3.0% ± 1.0 Ω
Output pulse: 5 volts peak to peak into open circuit. Pulse widths determined by range and cable
Velocity Factor: Variable from 0.2 to 0.99 in steps of 0.01
Gain: Set for each range with four user selectable steps
Refresh Rate:
Selectable from the menu. Once per second or three times a second
Backlight:

Stays on for 1 minute when activated

Display: 128 x 64 pixel Graphics LCD
Test Leads: 2 metres long consisting of 2 x 4mm shrouded connector to miniature crocodile clips
Connectors: Two 4mm-safety terminals
Batteries:
Six LR6 (AA) type batteries, Manganese alkali or nickel-cadmium or nickelmetal- hydride cells
 
 
Impedance: 25 Ω 50 Ω 75 Ω 100 Ω
10m 7ns 7ns 7ns 7ns
30m 20ns 20ns 20ns 20ns
100m 100ns 60ns 100ns 100ns
300m 300ns 120ns 170ns 300ns
1000m 1000ns 520ns 680ns 1000ns
3000m 3000ns 2020ns 2340ns 3000ns
 
  Downloads:  
space
 
  pdf_pic Downloads: General Specifications  
base

Safety:
This instrument complies with IEC61010-1 for connection to live systems up to 300 V CAT III. Fused leads must be used if the voltage between the terminals exceeds 300 V

EMC:
Complies with Electromagnetic Compatibility Specifications (Light industrial) BS EN 61326-1, with a minimum performance of ‘B’ for all immunity tests

Mechanical:
The instrument is designed for use indoors or outdoors and is rated to IP54.

Case Dimensions:
230 x 115 x 48 mm
9 x 4.5 x 2 Inches

Instrument weight:
0.6kg (1.32lbs)

Case material: ABS

Environmental

Operational Temperature:
-15ºC to +50ºC (5ºF to 122ºF)

Storage Temperature: -20ºC to 70ºC (-4ºF to 158ºF)

 
 