| General Specifications |
| Accuracy ( 23±3°C ) |
0.3% ro |
| Linearty & repeatability |
0.1% typical |
| Dielectric strength |
4KV rms AC between power / input & output terminals |
| Surge and impulse test |
ANSI C37.90 / 1989, IEC 255-3 (1989) 4 KV 1.2 x 50 us |
| Configuration |
Three wires connection / applicable for two wires
Excitation - 5mAdc constant current source
Changeable input module
Linearized output vs input temperature |
| Field rangeability |
Selectable output mode for voltage or current mode
Switchable of input range & output range
Switchable AC power 110V or 220V
Selectable degree C or F calibration |
| Effect of wire resistance |
Automatically eliminated for 3 wires connection
Offset recalibration required as for 2 wires connection |
| Input break detection |
Selectable Hi-set or Lo-set
Hi-set over 110% of rated output
Lo-set less 0.5% of rated output |
| Aux. power effect |
< 0.003% for per voltage change |
| Storage condition |
Temperature range -25 to 70°C, RH 20 to 95% non condensed |
| Operating condition |
Temperature range -20 to 55 °C, RH 0 to 99% non condensed |