Spacer Home Contact_us ob Opportunities ISO_Registration Privacy_Statement
 
Caption_Header
Hsiang Cheng Corp. ®
Model EPM7000,
PQM (Power Quality Meter)
 
previous URL Next URL
< Links >
 
 
green_line
 

Hsiang Cheng, EPM7000 Power Quality Meter

 
 
  Characteristics:  
space
green_line
 
 
  • For factory and building automation
  • Modbus®RTU protocol
  • Maximum 600V
  • True RMS conversion
  • LCD display
  • Field programmable PT / CT ratio
  • Accuracy up to 0.2%
  • Memory for all setup and energy data
  • Comprehensive self test diagnostics
  • Low input burden 0.1VA (5A / 120V)
  • Wide power supply range 80~260V AC / DC
  • Compact physical configuration
  • Compatible for DIN & ANSI cut out
  • 2KV RMS input / output / power isolation
 
 
  Product Description:  
space
green_line
 

space

EPM7000 digital power meters are an intelligent approach to traditional power metering. Each power meter is a compact, electronically advanced and easily programmable with a multi-display.

They are designed to be compatible with the most widely used DIN standard panel instruments (It fits the DIN 92 x 92 mm panel cutout holes).

Wiring is a breeze, you need only to connect one meter, it also uses standardized hardware suitable for either 1 phase 2 wires, 1 phase 3 wires, 3 phase 3 wire or 3 phase 4 wires networks. These high-tech power meter are highly dependable, come with an accuracy of 0.2% for voltage and current and up to 0.25%. for power measurement and long-term stability.

A large LCD screen with alphanumeric readout allows the user to manually or automatically prioritize and sequentially view the more than 30 electrical parameters.

This versatile power meter is equipped with a serial port (RS-485 or RS-232), to allow connection to an open architecture network. The Modbus® protocol aloows for communication to PCs or data acquisition systems . The EPM7000 software provides a simple yet practical solution to energy management in factories and plant, small industries, building services, etc.

 
 
  Features:  
space
green_line
 
 
  • Factory & Building Automation (FA & BA)
    The power meter was developed for factory and building automation (FA & BA) applications, more all of power and energy parameters can easily apply to wide range of AC switch-gear or industrial power distribution system for metering.
  • PLC Modbus Compatible
    The Modbus® communications protocol allows information and data to be efficiently transferred between EPM 7000 and modicon programmable logic controllers (PLC) or other third party Modbus® compatible monitoring and control system. The EPM 7000 can also establish a monitoring system by using an IPC-based centralized master display software. (The RTU mode Modbus® protocol with defaullt baud rate 9600 bps, 8 data bit.)
  • Memory for all setup and energy data
    All of the meter status settings and energy data is retained in a non-volatile memory. EPM 7000 power meter records includes measured watt-hours, PT and CT ratios, system configurations, display settings, and communication parameters.
  • Field Programmability
    The field programmable power meter is able to set e.g. CT and PT ratio, Modbus® address, communication baud rate, parity, meter’s display, etc. either programming by push-bottom or by rear RS-485 / RS-232 communication port from a PC.
  • Accuracy up to 0.2%
    Voltage and current up to 0.2% and other power up to 0.25%.
  • Comprehensive System Integration
    The PLC compatible RS-485 / RS-232 Modbus® communication protocol for efficient data transfer between the EPM 7000 and Modicon programmable logic controller (PLC) existing RTU Power SCADA systems and DCS systems or other Modbus protocol compatible systems.
 
 
  Specifications :  
 
green_line
 
Range:
Voltage : 10~600V
Current : suitable for CT secondary rating (optional)
Maximum 6A for 5A rating
Maximum 1.2A for 1A rating
Triggered trace memory / fault recording range V ≤ 600V
A ≤ 8 x rated
Frequency : 40 - 70Hz
Burden:  
Voltage: < 0.4VA at 600V
< 0.04VA at 150V
Current: < 0.1VA at 5A
Overload Capacity  
Voltage 750V continuous
1000V 10 seconds
1200V 3 seconds
Current 2 x rated continuous
10 x rated 30 seconds
25 x rated 2 seconds
50 x rated 1 seconds
Monitoring/inputs/outputs
Measured system Suitable for 3 phase 4 wires / 3 phase 3 wires / single phase 2 & 3 wires / 3 phase balance
Select by input wiring & software configuration
Programmability:

Software accessible / password lock

System selection : 3 phase 4 wires / 3 phase 3 wires /1 phase 2 & 3 wires and 3 phase balance

PT : 1 - 5000.0 ; CT : 1 - 2000.0

Readout display control 4 digits / auto scan or manual selection / scanning time
Communication Baud rate 1200 / 2400 / 4800 / 9600 / 19200
Address setting 1 - 254
Calibration : software with password lock
Memory : all of energy date and status setting
Normal Operation 250Vac / 30Vdc, 10A resistive
250Vac / PF 0.4, 6A inductive
30Vdc / t=7ms, 6A inductive
Interrupting Capacity 300Vac, 10A
250Vdc, resistive 0.32A maximum, t=7ms
125Vdc, resistive 0.5A maximum, t=7ms
Analog Input ( AI )
Accuracy, 0.5% fs
3 differential analog inputs / process variables
Standard input 4-20mA / 0-20mA
Common mode voltage E100V maximum
Option input 0-10V / 0-5V / 0-1V / 1-5V / 2-10V
Analog output (AO) Accuracy, 0.5% fs
4 isolated analog outputs
Standard output 4-20mAdc / load ≤ 500Ω
Configurable Measured parameters
Input range, unipolar / bipolar
Pulse Output ( PO ) 2 pulse outputs photo-isolated
Configurable
Parameter , WH / VarH / VAH / AH
Unit, ±1WH / ±1QH / 1VAH / 0.01AH
Pulse width / 50% duty cycle
Standard output: 4-20mAdc / load < 500Ω
Configurable Measured parameters Input range, unipolar / bipolar
General Specifications
Communication ports: RS485 ( standard ) ;
RS232 ( option )
Modbus® RTU protocol
Display:

LCD 0.4” display, 3 rows of 8 alphanumerics

RTC Maximum deviation 5 seconds in 24 hours
Time for year / month / day / hour / minute / sec
Dielectric strength: IEC 255-5
2KV AC rms 1 minute between input / output / power
Impulse and surge test: ANSI/IEEE C37.90.1-1989 (3KV) SWC test
IEC 255-22-1 class III SWC test
IEC 255-22-4 class IV (IEC 801-4) SWC test
IEC 255-5 1.2 x 50us (5KV) impulse test
Stability: Temperature range -25 to +55°C, maximum 100 ppm/°C
Long term stability 0.15% drift maximum per year
Operating condition: Temperature range -25 to +60°C,
RH 20 - 95% non-condensed
Storage condition: Temperature range -25 to +60°C,
RH 20 - 95% non-condensed
Power supply: AC 80-260V, 40-70Hz, DC 80-330V
DC 20-60V
Dissipation maximum 12VA for AC and 6 Watts for DC
Mounting / Dimension: Panel type mounting
DIN 120 x 120 x 130.5mm
Cut out : 92 x 92mm
 
 