- Accuracy:
0.5% fs MWX, MWY,MWZ, MWQ,MKX,MKY,MKQ (3-3/4 dgt)
0.25% fs+1 count: MWX4,MWY4,MWZ4,MWQ4,MKY4,MKZ4,MKQ4 (4-1/2 dgt)
- Temperature coefficient: < 60 ppm per degree C
- Long term drift < 0.2% per year
- 3-3/4 digits 3999 counts maximum
- 4-1/2 digits 19999 counts maximum
- Display 0.56"super rated LED
- Response time Sample rate 1 pf per sec typically
- Current Over Range: 3 X rating-continuous, 10X rating-30sec, 25X rating-3sec.
- Voltage Over Range: maximum continuous 750V or 1.5X rating
- Frequency Watt version: norminal 5Hz
- Var version: Norminal 0.5 hz < 0.2% change for 0.1 hz\
- Dielectric strength: 2.5 kvrms/ 1 minute, (case)
- 2 kvrms/ 1 minute, input terminals to power terminals
|
|
| |
| |
|
|
|
| |
|

|
The Model MW & MK measure active & reactive power, it can to measure a distorted sinusoidal wave with high harmonics or chopped SCR-conrolled waveforms. The ratio input model accepts a secondary signal from CTs & PTs and provides a direct reading. The direct input type is calibrated to the specified inputs to provide an accurate reading. |
|
| |
| |
|
|
| |
|
| |
| |
| Range: |
| Accuracy (23 + 3°C): |
MWX, MWY,MWZ, MWQ,MKX,MKY,MKQ
(3-3/4 digits)
0.5% fs or 5 cts. which ever greater :
MWX4,MWY4,MWZ4,MWQ4,MKY4,MKZ4,MKQ4
(4-1/2 digits)
0.25% fs + 1 count |
| Stability : |
Temperature coefficient < 50 ppm per degree C
Long term draft < 0.2% per year |
| Digits & counts: |
3/4 digits 3999 counts maximum,
4-1/2 digits 19999 counts maximum |
| Display : |
0.56” super rate LED |
| Ratio Configuration settable : |
Ratio settable : CT ratio for MAF, PT ratio for MVF |
| Response time : |
Sample rate 1 of per sec typically |
| input burden: |
0.25 VA maximum |
| input Overload: |
Current input: 3 * rating-continuous, 10 * rating-30 sec, 25 * rating-3sec
Voltage input: maximum continuous 750 V or 3 * rated which ever great |
| Frequency Watt version : |
norminal + 5Hz |
| Frequency Var version : |
norminal + 0.5 Hz < 0.2% change for 0.1 Hz deviated of center frequency |
| Crest factor |
Normally < 3 (MW series only) |
| Waveform |
3rd 30% for watt version only |
| Dielectric strength: |
2.5KV rms / 1 minute, all terminals to reference ground
2KV rms / 1 minute, input terminals to power terminals |
| Surge test: |
ANSI C37.90.1 / 1989, IEC 255-3 (1989)
|
| Impulse Voltage: |
1.2 * 50 us 4 KV |
| Oscillating wave : |
0.5us-100KHz 3KV or 1MHz-0.25 ms 2.5 KV |
| Operating condition |
Operating temperature :
-10 to 55°C, 0-99% RH non-condensed
Storage:
-25 to 70°C, 20-99% RH non-condensed |
| Auxiliary power AC / DC version: |
< 3.5 VA, DC option version ±20% < 5 Watts |
| Applied rules and standards |
| Measuring & conversion: |
IEC 688 |
| Dielectric strength: |
IEC 688
|
| Impulse & Surge test: |
ANSI C37.90.1/1989
IEC 255-3 (1989) |
| Adaptability-power system: |
IEC 0110 |
| Measuring reliability: |
VDE 3540 |
|
|
| |
| |
|
|
|
|
| |
| |
General Specifications |
|
|
|
|
|
 |
| |
Related urls: |
|
|
| |
- MA, MV, Average Reading
AC Current & Voltage Digital Panel Meters
- MAR, MVR True RMS,
AC Current & Voltage Digital Panel Meters
- MAF & MVF Series,
Frequency Digital Panel Meters
- MW & MK Series,
Digital AC Watts Var Meters
- MWF & MKF Series,
Programmable Watt and Var Meters
- MWH & MKH Series,
Programmable Watthour, Varhour Meters
- MF Series, Frequency Panel Meters
- MP and ML Series,
Power Factor & Phase Angle Panel Meters
- UFV & UFA Series, True RMS
AC Voltage and Current Digital Meters
|
| |
|
|
|
|
|
|
|