- Output Power:
3 kVA to 90 kVA
- Output Frequency: 45-500 Hz
- Output Voltage:
Dual range, 150-260 V or 300-520 V, 3 phase
- Isolated Linear Output, THD: < 1%
- Input Requirements: 220, 240, 380, 415, 480 VAC ± 10%, 3 phase, 47 - 63 Hz
Intuitive Front Panel
- Controls: Frequency and Voltage
- Easy to Read LED Displays: Frequency, Voltage, Current, Power and Power Factor
- Memory Locations: Can save three desired settings of any voltage, frequency and current limit covered in the output parameters
|
|
|
|
|
| |
| |
|
|
|
| |
| |
The APS3000 series consists of seven,3 phase output instruments
with an output power of 3 kVA to 90 kVA. These converters have a range of 45-500Hz with dual voltage ranges
from 0-150 volts or 0-300 volts. This allows the user to duplicate a 50 or 60 hertz
a utility grid and the ability to range up to 400 Hertz for
testing military/avionics electronics and instruments.
Setup and operation of the APS3000 series is exceptionally
easy. It is set via the front panel, allowing users to
continuously adjust voltage and frequency or to select
preset standard frequency settings. Universal power
outlets are provided on the front panel for ready access
to the controlled power.
Frequency, voltage, current, power or power factor are displayed on large LED Displays. |
|
| |
| |
|
|
|
| |
| |
| Model |
3003 |
3006 |
3009 |
3015 |
3030 |
3060 |
3090 |
| INPUT SPECIFICATIONS |
| Phase |
1Ø/2W + ground |
3Ø/3W + ground |
| Voltage |
230V ± 15% |
220, 240, 380, 415, 480V ± 10% |
| Frequency |
47 - 63 Hz |
| OUTPUT SPECIFICATIONS |
| Power Rating (Total Power) |
3kVA |
6kVA |
9kVA |
15kVA |
30kVA |
60kVA |
90kVA |
| Power Rating (Per Phase) |
1kVA |
2kVA |
3kVA |
5kVA |
10kVA |
20kVA |
30kVA |
| Max Arms per Ø @ 0-150 V |
8.4A |
16.8A |
25.2A |
42.0A |
84.0A |
168.0A |
252.0A |
| Max Arms per Ø @ 0-300 V |
4.2A |
8.4A |
12.6A |
21.0A |
42.0A |
84.0A |
126.0A |
| Phase |
3Ø/5W |
| Voltage |
| Line to Neutral |
0-150V / 0-300V Selectable |
| Line to Line |
0-260V / 0-520V Selectable |
| Resolution |
0.1V |
| Accuracy |
± (1% + 0.2V) |
| Frequency |
| Range |
45-500 Hz |
| Resolution |
0.1Hz at 45-99.9Hz, 1Hz at 100-500Hz |
| Accuracy |
± 0.2% |
| |
| Harmonic Distortion |
≤ 1% (Resistance Load) |
| Crest Factor |
≥ 3 to 1 |
| Load Regulation |
± 0.5% |
| Protection |
Over Current, Short Circuit, Over Temperature |
| Efficiency |
≥ 85% (at full load) |
| Operating Temperature |
32˚-104˚F, (0˚-40˚C), 80% Relative Humidity |
| Altitude |
below 6500 feet |
| DISPLAYS AND CONTROLS |
| 4 Digital LED meters |
Frequency, voltage, Current, Power or Power Factor (simultaneously) |
| PLC Remote Interface |
P1, P2, P3 and Output On/Off |
| Memory |
3 Programmable Memory Locations for voltage, Frequency and Current |
| Calibration |
Front Panel Calibration |
| Interface (optional) |
GPIB or RS-232 |
| Auto voltage adjust |
Enabled for improved voltage regulation within ± 0.1% |
| MECHANICAL SPECIFICATIONS |
| Dimensions (HxDxW) Inches |
34x26x17 |
32x36x24 |
38x36
x24 |
55x36
x24 |
TBD |
| Weights (kg/lbs) |
140/305 |
175/385 |
220/485 |
290/640 |
460/
1010 |
760/
1675 |
1200/
2640 |
|
|
| |
| |
|
|
|
| |
| |
Specifications |
|
|