- 4-quadrant Energy
- Energy Time of Use(TOU)
- Energy Reading
- Power Quality Analysis
- Waveform Capture
- Trend Record
- Sequence of Even(SOE)
- Over limit alarm
- Switch statues monitoring
- Remote switch controlling
Metering
- Voltage V1, V2, V3, Vlnavg, V12, V23, V31, Vllavg
- Current I1, I2, I3, In, Iavg
- Power P1, P2, P3, Psum
- Reactive Power Q1, Q2, Q3, Qsum
- Apparent Power S1, S2, S3, Ssum
- Frequency F
- Power Factor PF1, PF2, PF3, PF
- Energy Ep_imp, Ep_exp, Ep_total, Ep_net
- Reactive Energy Eq_imp, Eq_exp, Eq_total, Eq_net
- Demand Dmd_P, Dmd_Q, Dmd_S
Monitoring
- Power Quality:
- Voltage Harmonics 2nd to 31st and THD
- Current Harmonics 2nd to 31st and THD
- Voltage Crest Factor
- THFF (TIF)
- Current K Factor
- Voltage Unbalance Factor U_unbl
- Current Unbalance Factor U_unbl
- Max/Min Statistics with Time Stamps
- Switch Status
Alarms
- Up to 9 groups of alarm events could be recorded. The
monitoring objects can be chosen from 32 metering parameters: F, V1, V2, V3, Vlnavg, V12, V23, V31, Vllavg, I1, I2, I3, Iavg, In, P1, P2,
P3, Psum, Q1, Q2, Q3, Qsum, S1, S2, S3, Ssum, PF1, PF2, PF3, PF,
U_unbl, I_unbl, Dmd_P, Dmd_Q, Dmd_S
Display
- Clear and Large character LCD Screen display with blue back light
|
|
|
| |
| |
|
|
|
| |
| |
- Metering of distribution feeders, transformers, generators, capacitor banks and motors
- Medium and low voltage systems
- Commercial, industrial, utility
- Power quality analysis
|
|
|
| |
| |
|
|
|
| |

|
| The Acuvim series Intelligent Power Meter are an ideal choice when
continuous monitoring of a power system is required.
Programmable setpoints and two assignable outputs allow control
functions to be added for specific applications. This includes basic
alarm on over/under current, voltage, power, power factor, frequency,
unbalance factor or demand and pulse output based on Energy or
Reactive Energy. Status monitoring is possible using the 4 switch inputs.
It combines high accuracy measurement with intelligent multi-function
and simple HMI interface.
The Acuvim may be used to gather data from intelligent
Power Distribution Systems . All Data can be accessed via 485 communication
port running Modbus™ Protocol. Optional Ethernet , Profibus DP
communication and wireless
transmission add flexibility to all your application needs.
Power quality is important with increasing use of
electronic loads such as computers, ballasts or variable frequency
drives. Any phase current or voltage can be displayed and harmonic content calculated by
knowing the harmonic distribution. Action can be taken to prevent
overheated transformers, motors, capacitors, neutral wires and
annoying breaker trips. |
|
|
| |
| |
|
|
|
| |
| |
| Metering |
| Parameters |
Accuracy |
Resolution |
Range |
Voltage |
0.2% |
0.1% |
20V~500kV |
| Current |
0.2% |
0.02% |
0~9999 A |
| Power |
0.5% |
0.1% |
-9999~9999kW |
| Apparent Power |
0.5% |
0.1% |
0~9999kVA |
| Energy |
0.5% |
0.1% |
0~99999999.9kWh |
| Reactive Energy |
0.5% |
0.1KWh |
0~99999999.9kVarh |
| Apparent Energy |
0.5% |
0.1KVarh |
0~99999999.9kVAh |
| Power Factor |
0.5% |
0.1% |
-1.0~0~1.0 |
| Frequency |
0.2% |
0.01Hz |
45~65Hz |
| Energy |
0.5% |
0.1% |
0~9999kW |
| Reactive Energy |
0.5% |
0.1% |
0~9999kVar |
| Apparent Energy |
0.5% |
0.1% |
0~9999kVA |
| Current THD |
1.0% |
0.01% |
0~100.0% |
| Volts THD |
1.0% |
0.01% |
0~100.0% |
| Harmonics |
1.0% |
0.01% |
0~100.0% |
| Comminications |
| RS-485 (Optical Isolated) |
RS485 2 wire, half duplex, isolated
Baud Rate: 600 to 38400 bps |
|
|
| |
|||||||| Click here for Input, Control Power and Output Specifications
| Input |
| Current Inputs |
| Nominal Current |
5A Secondary (1A Secondary Option) |
| Full Scale |
120% of CT |
| Burden |
0.2VA |
| Overload |
2xCT for Continue
20xCT for 1 Second |
| Accuracy |
0.2% of Full Scale, True RMS |
| Voltage Inputs |
| Burden |
<0.2VA |
| PT Prim./Sec. |
Direct or 100~500,000:100~400 |
| Input Range |
20~400V |
| Accuracy |
0.2% full scale |
| Digital Input (DI) |
| Isolation Voltage: |
4000Vac RMS |
| Input Type: |
Wet Contact |
| Resistance: |
2K ohm (Typical) |
| Input Voltage: |
5~30Vdc |
| Close Contact Voltage: |
5Vdc |
| Max. Current |
20 mA |
| Digital Output |
| Relay Output (RO) |
| Type: |
Mechanical Contact |
| Max Voltage: |
250Vac, 100Vdc |
Configuration:
|
Form A |
| Isolate Voltage: |
2500Vac rms |
| Output Mode: |
Latch or Momentary (50-3000ms Configurable) |
| Max Current: |
3A |
| Contact Material: |
Silver Alloy |
| Pulse Output |
| Parameters: |
KWh(import), KWh(export), KWh(net), KWh(total),
KVarh (import), KVarh(export), KVarh(net), KVarh
(total) |
| Pulse Rate: |
1 to 6000 in steps of 1 (0.1 KWh or KVarh) |
| Pulse Width: |
20ms to 1000ms in step of 20ms |
| Min Pulse Interval: |
20ms |
| Alarm Output |
| Parameters: |
KWh(import), KWh(export), KWh(net), KWh(total),
KVarh (import), KVarh(export), KVarh(net), KVarh
(total) |
| Time Limit: |
0 to 76500ms in step of 300ms |
| Output Form: |
Open Collector, NO |
| Optical Isolated: |
4000Vac rms |
| Max Positive Voltage: |
40Vac |
| Max Negative Voltage: |
6Vdc |
| Max Positive Current: |
30mA |
|
| |
|||||||| Click here for Operating Specifications and Size
| Operating Environment |
| General |
| Operation Temp. |
- 25ºC to 70ºC |
Storage Temp.
|
- 40ºC to 85ºC |
| Relative Humidity |
95% non-condensing |
| Power Supply |
| Input: |
100V~240Vac 50/60Hz
100V~300Vdc |
| Maximum power |
2W |
| Dimensions |
| Size |
165mm×140mm×115mm |
|
| |
| |
|
|
|
| |
| |
Specifications |
|
|