Acuvim-S, Digital, Multi-Function Power Meters
 
  Characteristics:  
 
 
  • 4-quadrant Energy
  • Energy Time of Use(TOU)
  • Energy Reading
  • Power Quality Analysis
  • Waveform Capture
  • Trend Record
  • Sequence of Even(SOE)
  • Over limit alarm
  • Switch statues monitoring
  • Remote switch controlling
Metering
  • Voltage V1, V2, V3, Vlnavg, V12, V23, V31, Vllavg
  • Current I1, I2, I3, In, Iavg
  • Power P1, P2, P3, Psum
  • Reactive Power Q1, Q2, Q3, Qsum
  • Apparent Power S1, S2, S3, Ssum
  • Frequency F
  • Power Factor PF1, PF2, PF3, PF
  • Energy Ep_imp, Ep_exp, Ep_total, Ep_net
  • Reactive Energy Eq_imp, Eq_exp, Eq_total, Eq_net
  • Demand Dmd_P, Dmd_Q, Dmd_S
Monitoring
  • Power Quality:
  • Voltage Harmonics 2nd to 31st and THD
  • Current Harmonics 2nd to 31st and THD
  • Voltage Crest Factor
  • THFF (TIF)
  • Current K Factor
  • Voltage Unbalance Factor U_unbl
  • Current Unbalance Factor U_unbl
  • Max/Min Statistics with Time Stamps
  • Switch Status
Alarms
  • Up to 9 groups of alarm events could be recorded. The monitoring objects can be chosen from 32 metering parameters: F, V1, V2, V3, Vlnavg, V12, V23, V31, Vllavg, I1, I2, I3, Iavg, In, P1, P2, P3, Psum, Q1, Q2, Q3, Qsum, S1, S2, S3, Ssum, PF1, PF2, PF3, PF, U_unbl, I_unbl, Dmd_P, Dmd_Q, Dmd_S
Display
  • Clear and Large character LCD Screen display with blue back light
 
 
  Applications:  
 
 
  • Metering of distribution feeders, transformers, generators, capacitor banks and motors
  • Medium and low voltage systems
  • Commercial, industrial, utility
  • Power quality analysis
 
 
  Product Description:  
 

space

The Acuvim series Intelligent Power Meter are an ideal choice when continuous monitoring of a power system is required.

Programmable setpoints and two assignable outputs allow control functions to be added for specific applications. This includes basic alarm on over/under current, voltage, power, power factor, frequency, unbalance factor or demand and pulse output based on Energy or Reactive Energy. Status monitoring is possible using the 4 switch inputs. It combines high accuracy measurement with intelligent multi-function and simple HMI interface.

The Acuvim may be used to gather data from intelligent Power Distribution Systems . All Data can be accessed via 485 communication port running Modbus™ Protocol. Optional Ethernet , Profibus DP communication and wireless transmission add flexibility to all your application needs.

Power quality is important with increasing use of electronic loads such as computers, ballasts or variable frequency drives. Any phase current or voltage can be displayed and harmonic content calculated by knowing the harmonic distribution. Action can be taken to prevent overheated transformers, motors, capacitors, neutral wires and annoying breaker trips.

 
 
  Specifications:  
 
 
Metering
Parameters Accuracy Resolution Range

Voltage

0.2% 0.1% 20V~500kV
Current 0.2% 0.02% 0~9999 A
Power 0.5% 0.1% -9999~9999kW
Apparent Power 0.5% 0.1% 0~9999kVA
Energy 0.5% 0.1% 0~99999999.9kWh
Reactive Energy 0.5% 0.1KWh 0~99999999.9kVarh
Apparent Energy 0.5% 0.1KVarh 0~99999999.9kVAh
Power Factor 0.5% 0.1% -1.0~0~1.0
Frequency 0.2% 0.01Hz 45~65Hz
Energy 0.5% 0.1% 0~9999kW
Reactive Energy 0.5% 0.1% 0~9999kVar
Apparent Energy 0.5% 0.1% 0~9999kVA
Current THD 1.0% 0.01% 0~100.0%
Volts THD 1.0% 0.01% 0~100.0%
Harmonics 1.0% 0.01% 0~100.0%
Comminications
RS-485 (Optical Isolated) RS485 2 wire, half duplex, isolated
Baud Rate: 600 to 38400 bps
 
|||||||| Click here for Input, Control Power and Output Specifications
Input
Current Inputs
Nominal Current 5A Secondary (1A Secondary Option)
Full Scale 120% of CT
Burden 0.2VA
Overload 2xCT for Continue
20xCT for 1 Second
Accuracy 0.2% of Full Scale, True RMS
Voltage Inputs
Burden <0.2VA
PT Prim./Sec. Direct or 100~500,000:100~400
Input Range 20~400V
Accuracy 0.2% full scale
Digital Input (DI)
Isolation Voltage: 4000Vac RMS
Input Type: Wet Contact
Resistance: 2K ohm (Typical)
Input Voltage: 5~30Vdc
Close Contact Voltage: 5Vdc
Max. Current 20 mA
Digital Output
Relay Output (RO)
Type: Mechanical Contact
Max Voltage: 250Vac, 100Vdc
Configuration:
Form A
Isolate Voltage: 2500Vac rms
Output Mode: Latch or Momentary (50-3000ms Configurable)
Max Current: 3A
Contact Material: Silver Alloy
Pulse Output
Parameters: KWh(import), KWh(export), KWh(net), KWh(total),
KVarh (import), KVarh(export), KVarh(net), KVarh
(total)
Pulse Rate: 1 to 6000 in steps of 1 (0.1 KWh or KVarh)
Pulse Width: 20ms to 1000ms in step of 20ms
Min Pulse Interval: 20ms
Alarm Output
Parameters: KWh(import), KWh(export), KWh(net), KWh(total),
KVarh (import), KVarh(export), KVarh(net), KVarh
(total)
Time Limit: 0 to 76500ms in step of 300ms
Output Form: Open Collector, NO
Optical Isolated: 4000Vac rms
Max Positive Voltage: 40Vac
Max Negative Voltage: 6Vdc
Max Positive Current: 30mA
 
|||||||| Click here for Operating Specifications and Size
Operating Environment
General
Operation Temp. - 25ºC to 70ºC
Storage Temp.
- 40ºC to 85ºC
Relative Humidity 95% non-condensing
Power Supply
Input: 100V~240Vac 50/60Hz
100V~300Vdc
Maximum power 2W
Dimensions
Size 165mm×140mm×115mm
 