Spacer Home Contact_us ob Opportunities ISO_Registration Privacy_Statement
 
Caption_Header

AEMC®Instruments

Model 8230 [Catalog No. 2130.81]
1Ø-Phase Power Quality Analyzer
 
previous URL Next URL
< Links >
 
 
 
Model 8230 [Catalog No. 2130.81] 1Ø-Phase Power Quality Analyzer

Characteristics:

  • Measures up to 660Vrms or VDC
  • Measures up to 6500AAC or 1400ADC (probe dependent)
  • Displays Min, Max and Average Volts and Amps, Crest Factor, Peak value and K-Factor
  • Calculates and displays Watts, VARs and VA, Power Factor and Displacement Power Factor for single-phase and balanced three-phase
  • Displays total harmonic distortion (THD-F and THD-R) for voltage and current
  • Displays individual harmonic values and % for Volts and Amps through the 50th harmonic
 
  Characteristics (cont'd) :  
 
 
  • Captures, displays and stores inrush current waveforms and statistics
  • Stores up to eight screen captures
  • Stores up to 1MB of trend recorded data
  • Configurable from DataView® software or front panel
  • Download stored data to DataView® software via optical with isolated USB port
  • Captures up to 4096 alarm events using up to 10 different thresholds
  • Displays and records up to 17 different power quality parameters
  • Includes DataView® software FREE.
 
 
  Application:  
 
 
  • Motor start-up analysis
  • Verification of power distribution circuits
  • Measurement and recording of power system quality (kW, VA, VAR)
  • Energy metering (kVAh, VARh, kWh)
  • In-plant troubleshooting of power distribution panels and individual machinery
  • Determine harmonic problems originating from source or load
 
 
  Product Description:  
 
space

The PowerPad® Jr. Model 8230 is a single-phase power quality analyzer that is easy-to-use, compact and shock-resistant. It is intended for technicians and engineers to measure and carry out diagnostic work and power quality work on single- or three-phase balanced load networks. Users are able to obtain instant waveforms of an electrical network’s principal characteristics, and also monitor their variation over a period of time. The multi-tasking measurement system simultaneously handles all the measurement functions and waveform display of the various magnitudes, detection, continuous recordings and their display without any constraints.

 
Models Available:
 

Model 8230 with MN93 [Catalog No. 2130.82]
Single-Phase Power Quality Analyzer PowerPad® Jr. Model 8230 with MN93 (240A)

Model 8230 with SR193 [Catalog No. 2130.83]
Single-Phase Power Quality Analyzer PowerPad® Jr. Model 8230 w/SR193(1200A)

Model 8230 with AmpFlex® 193-24 [Catalog No. 2130.84]
Single-Phase Power Quality Analyzer PowerPad® Jr. Model 8230 w/AmpFlex® 193-24 (6500A)

Model 8230 with AmpFlex® SR193-36 [Catalog No. 2130.85]
Single-Phase Power Quality Analyzer PowerPad® Jr. Model 8230 w/AmpFlex® 193-36 (6500A)

Model 8230 with MR193 [Catalog No. 2130.86]
Single-Phase Power Quality Analyzer PowerPad® Jr. Model 8230 with MR 193 (1000AAC/1400ADC)

Model 8230 with MN193 [Catalog No. 2130.87]
Single-Phase Power Quality Analyzer PowerPad® Jr. Model 8230 with MN193 (6A/120A)

 
 
  Features:  
 
space
  • Waveforms – Display Volts, Amps, THD and Crest Factor by phase or for all phases. You can display all the voltage inputs on one screen, phase-to-phase or phase-to-neutral. Real-time phasor diagrams can be displayed for volts and amps.
  • Harmonics – Display Harmonics out to the 50th for Volts, Amps and VA. Individual Harmonics are displayed as a percentage and in real value. Harmonic direction and sequencing can also be displayed.
  • Transients – Set, capture and display transients. You select the threshold and the number of transients to capture. PowerPad then captures four waveforms for each transient; the triggering waveform as well as one pre- and two post-triggered waveforms.
  • Alarms – Configure, capture and display alarm events. Each captured alarm event will show the variable and the value as well as the time and duration.
  • Record – Set up and record trend data at selectable rates from one sample/second to one sample every 15 minutes on as many as 22 different variables for all phases.
 
 
  Specifications:  
 
 
Model 8230
ELECTRICAL  
Sampling Frequency 256 samples per cycle
Voltage (TRMS) 660V
Current (TRMS)

MN Clamp: 5mA to 120A or 2 to 240A
MR Clamp: 10 to 1000AAC, 10 to 1400ADC
SR Clamp: 0 to 1200A
AmpFlex®: 0 to 6500A

MEASUREMENT RANGE RESOLUTION ACCURACY
RMS Voltages 15 to 600V 0.1V ±0.5% ± 2cts
DC Voltage Component 15 to 600V 0.1V ±1% ± 2cts
Phase Peak Voltages 15 to 600V 1V ±(1% + 5cts)
Frequency (Hz) 40 to 70Hz 0.01Hz ±0.01Hz
Current Probes (Arms)      
MN Clamp 0 to 240A 0.1A ±(0.5% + 2cts)
SR Clamp 0 to 1200A 0.1A;
1A ≥ 1000A
±(0.5% + 2cts)
AmpFlex® Probe 10 to 6500A 0.1A;
1A ≥ 1000A
±(0.5% + 1A)
       
Active Power (kW) 0 to 9999kW 4 digits
(10,000ct)
±1% ± 1ct @ PF
≥0.8
Reactive Power (kVAR) 0 to 9999kVAR 4 digits
(10,000ct)
±1% ± 1ct @ PF
≤0.8
Apparent Power (kVA) 0 to 9999kVA 4 digits
(10,000ct)
±1% ± 1ct
Power Factor
(PF & DPF)
-1.000 to 1.000 0.001 ±(1.5% + 0.01)
Active Energy (kWh) 0 to 9999MWh 4 digits
(10,000ct)
±1% ± 1ct @ PF
≥0.8
Reactive Energy (kVARh) to 9999MVARh 4 digits
(10,000ct)
±1% ± 1ct @ PF
≤0.8
Apparent Energy (kVAh) 0 to 9999MVAh 4 digits
(10,000ct)
±1% ± 1ct
Harmonics
(1st to 50th)
0 to 999% 0.1% ±1% + 5cts
K-factor (Akf) 1 to 99.99 0.01 ±5% ± 1ct
Flicker (PST) 0.00 to 9.99 0.01 – –
GENERAL  
Display 1/4 VGA (320 x 240) color LCD
Power Source NiMH AA rechargeable battery pack
AC Supply: 120/230VAC (50/60Hz)
Power Source
Battery Life
≥Eight hrs with display on
≥40 hrs with display off (recording mode)
Operating Temperature 32° to 122°F (0° to 50°C)
Storage Temperature -4° to 122°F (-20° to +50°C)
Dimensions 8.3 x 4.3 x 2.4" (211 x 108 x 60mm)
Weight 1.9 lbs (0.88kg)
SAFETY  
Rating EN 61010, 600V Cat. III, Pollution Degree 2
 
 
  Downloads:  
 
  pdf_pic Downloads: Specifications  
base
 
 
Scroll down
 
scroll
 
  scroll up  
 