AEMC®Instruments

Model 8220 [Cat. 2130.90] Power Quality Meter

space
Model 8220 [Catalog No. 2130.90] Power Quality Meter
Characteristics:
  • Measures up to 660Vrms or VDC
  • Measures up to 6500AAC or 1400ADC (probe dependent)
  • Displays Min, Max and Avg Volts and Amps, Crest Factor, Peak and K-Factor
  • Calculates and displays Watts, VARs and VA, Power Factor and Displacement Power Factor for single-phase and balanced three-
  • Displays THD for voltage and current
  • Displays individual harmonic values for Volts and Amps through the 50th harmonic
  • Captures and displays inrush current phase rotation and RPM
  • Displays temperature in °F or °C
  • Displays resistance up to 2000Ω/conducts continuity & diode tests
  • Stores up to nine complete sets of readings for all volt, amp, power, harmonics and other measurements
  • Configurable from DataView® software or front panel
  • Includes DataView® software free for data download and storage, real-time waveform display, analysis and report generation
Application:
  • Motor start-up analysis
  • Determine phase rotation and motor RPM
  • Detect hot spots in wiring and equipment
  • Verification of power distribution circuits
  • Measurement and recording of power system quality(kW, VA, VAR)
  • Energy metering (kVAh, VARh, kWh)
  • In plant troubleshooting of power distribution panels and individual machinery
Product Description:
space
space
The Model 8220 is a single-phase AC + DC power meter with an electroluminescent backlit digital display and is rated to 600V Cat III.It is a measurement tool for electrical parameters and distribution network disturbances, enabling the user to obtain instant measurements of the main characteristics of a single-phase network (voltage, current, power, voltage and current harmonics, etc.) and to monitor machinery in operation (temperature, inrush current and duration of operation, distance of windings and rotational speed). The Model 8220’s accuracy is better than 1% (excluding current sensors). It has a great flexibility due to AEMC’s range of current sensors, measuring from a few hundred milliamps to several thousand amps. The Model 8220 is designed for technicians, control and maintenance engineers, as well as electrical contractors and educators.
space
Models Available:
space

Model 8220 with MN93 [Catalog No. 2130.91] Power Quality Meter Model 8220 w/MN93 (240A)

Model 8220 with SR193 [Catalog No. 2130.92] Power Quality Meter Model 8229 w/SR193 (1200A)

Model 8220 with AmpFlex® 193-24 [Catalog No. 2130.93] Power Quality Meter Model 8220 w/AmpFlex® 193-24 (6500A)

Model 8220 with AmpFlex® 193-36 [Catalog No. 2130.94] Power Quality Meter Model 8220 w/AmpFlex® 193-36 (6500A)

Model 8220 with MR193 [Catalog No. 2130.95] Power Quality Meter Model 8220 w/MR193 (1000AAC/1400ADC)

Model 8220 with MN193 [Catalog No. 2130.96] Power Quality Meter Model 8220 w/MN193 (6A/120A)

space
Features:
space
  • Waveforms – Display Volts, Amps, THD and Crest Factor by phase or for all phases. You can display all the voltage inputs on one screen, phase-to-phase or phase-to-neutral. Real-time phasor diagrams can be displayed for volts and amps.
  • Harmonics – Display Harmonics out to the 50th for Volts, Amps and VA. Individual Harmonics are displayed as a percentage and in real value. Harmonic direction and sequencing can also be displayed.
  • Transients – Set, capture and display transients. You select the threshold and the number of transients to capture. PowerPad then captures four waveforms for each transient; the triggering waveform as well as one pre- and two post-triggered waveforms.
  • Alarms – Configure, capture and display alarm events. Each captured alarm event will show the variable and the value as well as the time and duration.
  • Record – Set up and record trend data at selectable rates from one sample/second to one sample every 15 minutes on as many as 22 different variables for all phases.
Specifications:
space
Model 8220
ELECTRICAL
Sampling Frequency 256 samples per cycle
Voltage (TRMS) Phase-to-Phase: 660VPhase-to-Neutral: 600V
Current (TRMS) MN Clamp: 5mA to 120A or 2 to 240AMR Clamp: 10 to 1000AAC, 10 to 1400ADC SR Clamp: 0 to 1200A AmpFlex®: 0 to 6500A
MEASUREMENT RANGE RESOLUTION ACCURACY
RMS Voltages 15 to 600V 0.1V ±0.5% ± 2cts
DC Voltage Component 15 to 600V 0.1V ±1% ± 2cts
Phase Peak Voltages 15 to 600V 1V ±(1% + 5cts)
Frequency (Hz) 40 to 70Hz 0.01Hz ±0.01Hz
Current Probes (Arms)
MN Clamp 0 to 240A 0.1A ±(0.5% + 2cts)
SR Clamp 0 to 1200A 0.1A;1A ≥ 1000A ±(0.5% + 2cts)
AmpFlex® Probe 10 to 6500A 0.1A;1A ≥ 1000A ±(0.5% + 1A)
Active Power (kW) 0 to 9999kW 4 digits(10,000ct) ±1% ± 1ct @ PF ≥0.8
Reactive Power (kVAR) 0 to 9999kVAR 4 digits(10,000ct) ±1% ± 1ct @ PF ≤0.8
Apparent Power (kVA) 0 to 9999kVA 4 digits(10,000ct) ±1% ± 1ct
Power Factor(PF & DPF) -1.000 to 1.000 0.001 ±(1.5% + 0.01)
Harmonics(1st to 50th) 0 to 999% 0.1% ±1% + 5cts
K-factor (Akf) 1 to 99.99 0.01 ±5% ± 1ct
Phase Rotation
RPM NA NA NA
Diode Test
Continuity
Resistance 2000Ω NA NA
Temperature °F or °C NA NA
GENERAL
Display Three-line backlit digital display with custom icons
Communication Port Optically isolated USB
Power Source NiMH AA rechargeable battery packAC Supply: 120/230VAC (50/60Hz)
Power SourceBattery Life ≥Eight hrs with display on≥40 hrs with display off (recording mode)
Operating Temperature 32° to 122°F (0° to 50°C)
Storage Temperature -4° to 122°F (-20° to +50°C)
Dimensions 8.3 x 4.3 x 2.4″ (211 x 108 x 60mm)
Weight 1.9 lbs (0.88kg)
SAFETY
Rating EN 61010, 600V Cat. III, Pollution Degree 2
space
pdf_pic Downloads: Specifications
base
Related urls: