The DTR® Model 8500 s is designed for on-site
testing of power, potential and current
transformers. When connected to a
non-energized transformer, the DTR®
Model 8500 accurately measures
primary to secondary turns ratio, while
simultaneously displaying polarity
and excitation current.
The DTR® is fully automatic and uses
an ANSI/IEEE compliant test method.
No user calibration, range selection,
hand cranking or tedious balancing
is required. At each measurement,
the DTR® automatically self-calibrates
and checks for open windings/
connections/ circuit breakers, short
circuits (excess excitation current),
incorrect test lead placement, and
reverse polarity.
The DTR® Model 8500 is designed
with operator safety in mind. Tests
are performed at low voltage and,
unlike other ratiometers, step-down
excitation is employed. This method,
in conjunction with an integral H/X
reverse protection circuit, guards
against the generation of hazardous
test voltages normally associated
with transformer ratio measurement
instruments.
A large, dual line alpha-numeric LCD
display with adjustable contrast and
backlight guarantees day/night readability.
Power is supplied by integral
NiCD battery (included) or by AC line.
Batteries are charged automatically
during AC operation. |
|
|
|
|
| |
|
| |
|
|
| |
|
|
|
|
| |
| |
- Designed for power transformers, VTs, PTs and CTs
- Direct readings from 0.8000:1 to 1500.0:1
- Display turns ratio, polarity and excitation current simultaneously
- Dual power supply and operation: integrated rechargeable NiCD battery and AC supply
- Display warnings of incorrect lead connections, reverse polarity, open and short circuits
- Easy connection and test setup: no
calibration or balancing required
- Large dual line display with
adjustable contrast and backlight
ensures clear day/night visibility
- Low battery indicator
- Includes 15 ft leads
|
|
| |
| |
|
|
|
| |
| |
- Power transformers
- Potential transformers
- Current transformers
|
|
| |
| |
|
|
|
| |
|

|
The DTR-8500 is a portable digital transformer ratiometer designed for on-site testing of power, potential and current transformers. When connected to a non-energized transformer, the DTR-8500 accurately measures primary to secondary turns ratio, while simultaneously displaying polarity and excitation current.
Rugged and reliable, the DTR-8500 is built into an attractive, sealed structural polypropylene case designed to withstand the rigors of industrial and utility field use. |
|
| |
| |
|
|
|
| |
| |
| Model |
DTR8500 |
| Ratio Range |
Auto-Ranging, 0.8000 to 1500.0:1 |
| Accuracy |
Ratio <10 to 1: ±0.2% of Reading
Ratio ≤10 to 1000 to 1: ±0.1% of Reading
Ratio >1000 to 1: ±0.2% of Reading |
| Excitation Signal |
PT/VT Mode: 44Vrms maximum
CT Mode: 0 to 1A Auto Level, 0.1 to 5Vrms |
| Excitation Current Display |
Range: 0 to 1000mA; Accuracy: ±2% of Reading ± 2mA
|
| Excitation Frequency |
70Hz |
| |
|
| Display |
LCD Character, 20 x 2, large format, LED backlight, day/night visible |
| Measurement Method |
In accordance with ANSI/IEEE C57.12.90 |
| Power Source |
Dual operation; rechargeable NiCD battery & 115/230V, 50/60Hz line supply.DTR® may be changed from 115/230V by internal switch at any time. Units available with factory presetting of 115 or 230V. |
| Batteries |
12V, 5 x 2 NiCD packs, 1300mAH, Panasonic
P-130SCR or equivalent |
| Battery Life |
Up to 10 hrs continuous operation. May be used while recharging. Low battery LCD indication. |
| Charging Time |
14 hrs typical, C/10 rate |
| Line Fuse |
115V: 1.0A, 5 x 20mm, slow acting
230V: 0.5A, 5 x 20mm, slow acting |
| Displayed Measurements |
Turns ratio; RMS excitation current; polarity |
| Displayed Messages |
Incorrect lead connections; H/X reversal (accidental step-up misconnection);
Short (excess excitation current); Open circuits; Circuit continuity & low battery |
|
|
| |
| General Specifications |
| Connections |
Cannon® XLR connectors and large color-coded industrial clips |
| Leads |
15 ft, H x X color-coded, in carrying bag |
| Display |
Dual line alpha-numeric 3.875 x 0.875" with contrast adjustment and backlight |
| Operating Temperature |
32° to 122°F (0° to 50°C), 0 to 90% RH (without condensation) |
| Case |
Heavy duty structural polypropylene (yellow) |
| Dimensions |
13 x 12 x 6" (330 x 305 x 152mm) |
| Weight |
14 lb (6.4kg) |
|
| |
| |
|
|
|
| |
| |
Specifications |
|
|
|
 |
| |
 |
|
|
.jpg) |
|