AEMC®Instruments

Model 6501 [Cat. 2126.51] Megohmmeter (Hand-cranked)

space
space
Model 6501 Megohmmeter (Hand-cranked)
Characteristics:
  • True Megohmmeter®
  • Test voltages to 500V
  • Insulation measurements to 500MΩ
  • LED indicates constant voltage output and proper cranked speed
  • Automatic discharge when measurement is finished
  • Auto-Ranging – dual scale operation for better sensitivity and easier reading
  • Designed for harsh environments: marine, mining, heavy-duty field, industrial and military use
  • Extra rugged cast aluminum case, O-ring sealed against rain, water and dust; aluminum lid
  • Compact, self-contained package; folded crank
  • Large direct-reading scale
  • CE Mark
Application:
  • Acceptance testing and preventive maintenance
  • Test motors, cables, switchgears and electrical wiring installations
  • Continuity checks
  • Check domestic and industrial contracting
Product Description:
space
space The Megohmmeter Model 6501 is a compact, self-contained, hand-cranked True Megohmmeter®. This practical and dependable instrument is designed for a broad range of plant and field service applications, such as acceptance testing and preventive maintenance of wiring, cables, switchgear and motors. The easy hand-cranked operation provides a steady, DC voltage output across the entire range for consistently reliable readings. In addition to insulation resistance testing at 500V, the Model 6501 also permits resistance testing to 500kΩ and continuity testing to 100Ω. The 600V test voltage range is to perform safety checks to confirm that the sample is fully discharged and not connected to an energized circuit.
space
Specifications:
space
ELECTRICAL Model 6501
INSULATION TESTS
Test Voltage 250V 0.5 to 5.5MΩ;5.5 to 200MΩ
500V 0.5 to 5.5MΩ;5.5 to 200MΩ
1000V 0.5 to 5.5MΩ;5.5 to 200MΩ
Short Circuit Current 5mA (max)
Accuracy 2.5% of Full Scale Length
Automatic Discharge 5s/μF
Charge Time 250V 0.5s/μF
500V 0.5s/μF
1000V 0.5s/μF
RESISTANCE TESTS
Measurement Range 0 to 45kΩ45 to 500kΩ
Test Current 1mA constant current
Accuracy 2.5% of Full Scale
Automatic Discharge 5s/μF
Charging Time 0.5s/μF
CONTINUITY TESTS
Test Voltage 5mADC(10V max)
Measurement Range 0 to 9;10 to 100Ω
Accuracy 2% of Full Scale