The Digital Ground Resistance Tester
Model 6470 performs grounding
resistance, soil resistivity, bonding tests
(2- and 4-wire Resistance) and earth
coupling measurements. This direct
reading tester measures from 0.01 to
99.99kΩ, and is auto-ranging,
automatically seeking out the optimum
measurement range test current and test
frequency.
Easy-to-use — simply
connect the leads, select the test mode,
Press-to-Measure and read the results.
Up to 512 test results can be stored in
internal memory for later recall to the
display or download to a PC for analysis
and hard copy reports.
The large LCD is easy-to-read and
indicates grounding electrode
resistance, test voltage, current and
frequency. It also measures individual
test electrode resistance, battery status
and more depending on the
measurement.
The Model 6470 is Cat IV rated to 50V
and is over voltage protected to greater
than 250V against accidental
connection to live circuits. Live voltage,
if present, is also displayed on screen.
In the event of a system fault, the
Model 6470 can withstand 250V
between any two terminals.
Also included, are manual and
automatic test frequency selection from
40 to 513Hz; user selectable Soil
Resistivity test method (Wenner or
Schlumberger); user selectable 2-Wire
or 4-Wire Bond Resistance test
and a Earth coupling test feature.
Additional features of the Model 6470
include: a heavy-duty field case sealed
against dust and water when closed
(the test button is also sealed against
the elements); NiMH rechargeable
batteries. An external charger powered
from 120V/230V 50/60Hz is included.
The Model 6470 can also be powered
and charged from a 12V vehicle battery.
Testing while recharging is allowed.
The Ground Resistance Tester Model
6470 is rugged, easy-to-use and
ideal for maintenance crews and
contractors performing numerous tests.
It exceeds mechanical and safety
specifications for shock, vibration and
drop tests called out in IEC standards.
The adjustable test frequency and
filtering provide for rejection of high
levels of interference, allowing it to be
used under difficult conditions such as
the presence of high stray currents that
normally affect accuracy, and measured
auxiliary rod resistance enables the
user to optimize measurements in
difficult soil environments. |
.jpg) |
|
|
|
| |
|
| |
![Model 6470 [Catalog No. 2135.01] 4-Point Ground Resistance Testers](/Assets/jpgs/AEMC/Ground_Testers/2135.01.jpg) |
- 3-Point Fall-of-Potential measurement
- 3-Point earth coupling measurement
- Manual or automatic frequency scan from 40 to 513Hz for test accuracy in electrically noisy environments
- Earth coupling testing
- Selectable test voltage 16 or 32V up to 250mA test current
- 4-Point soil resistivity measurement with automatic calculation of Rho and user selection of Wenner or Schlumberger test method
|
|
|
|
| |
|
|
|
|
| |
| |
- 2- and 4-Wire DC resistance measurement (Bond testing) with automatic polarity reversal
- Auto-off power management
- Automatic recognition of all electrode connections and their resistance value
- Stores up to 512 complete test results in internal memory
- Optically isolated USB communication
- Remote set up and operation of all measurements using DataView® software supplied
- Rechargeable NiMH batteries from wall charger or vehicle power
- Rugged dustproof and rainproof field
- Includes DataView® software
|
|
| |
| |
|
|
|
|
| |
| |
- 3-Point measurements of resistance to ground of ground rods and grids. 3-Point measurements are used when electrode or grid can be easily disconnected.
- 4-Point tests or soil resistivity measurements. Locating areas of lowest soil resistivity is essential for achieving an economical grounding installation.
- Touch and step potential testing measurements. These tests are recommended when the ground cannot be disconnected, where ground faults are highly likely to occur, or when the “footprint” of grounded equipment (the outline of the part of equipment in contact with earth) is comparable to the size of the ground to be tested.
- 2- or 4-Wire tests for continuity tests on bonding or on grounding systems. Test is a DC resistive test using 250mA or more and is used to check bonding of all connection points on the ground system.
- Earth coupling measurement and display. Used to estimate the influence of two earth resistance systems that are not connected to each other.
|
|
| |
| |
|
|
|
| |
| |
The Digital Ground Resistance Tester Model 6470 performs grounding resistance, earth coupling measurement, soil resistivity and bonding tests. This direct reading tester measures from 0.01 to 99,000 Ω, and is auto-ranging, automatically seeking out the optimum measurement range test current and test frequency. Easy-to-use — simply connect the leads, select the test mode, Press-to-Measure and read the results. Up to 512 test results can be stored in internal memory for later recall to the display or download to a PC for analysis and hard copy reports. |
|
| |
| |
|
|
|
| |
| |
| ELECTRICAL |
Model 6470 |
| 3-point Measurement |
|
Range
(auto) |
0.01Ω to 99.99kΩ |
| Measurement |
0.01Ω to 100Ω |
| Resolution |
Nominal 16 or 32V user selectable |
| Test Voltage |
40 to 513Hz user selectable or automatic selection |
| Resistance Measurement
Frequency |
Up to 250mA |
| Accuracy |
±2% of Reading + 1ct |
| Earth Coupling Meas. |
Yes |
| Soil Resistivity |
|
| Test Method |
Wenner or Schlumberger selectable with automatic calculation of test results in Ω-meters or Ω-feet |
| Range
(auto) |
0.01 to 99.99kΩ |
| Resolution |
0.01 to 100Ω |
| Test Voltage |
16 or 32V user selectable |
| Frequency |
73, 91.5, 101, 110 or 128Hz selectable |
| External Voltage Meas. |
|
| Range
(auto) |
0.1 to 65.0V – DC to 500Hz |
| Accuracy |
2% of Reading + 2cts |
| Resistance Measurement (Bond Testing) |
| Measurement Type |
2-Point (with lead resistance compensation) or 4-Point (Kelvin sensing) user selectable |
| Range (Auto-Ranging) |
2-Point 0.01Ω to 99.9kΩ; 4-Point 0.001Ω to 99.99kΩ |
| Accuracy |
±2% of Reading + 2cts |
| Test Voltage |
16VDC (+, – or auto polarity) |
| Test Current |
Up to 250mA max |
| Data Storage |
|
| Memory Capacity |
512 test results |
| Communication |
Optically isolated USB |
| Automatic Report Generation |
Yes – tabular listings and Fall-of-Potential plots |
| |
|
| Power Source |
Eight 1.2V NiMH rechargeable batteries |
| Recharging Source |
110/220 50/60Hz external charger with 18VDC, 1.9A output or 12 VDC vehicle power |
|
|
| |
| General Specifications |
| Display |
Custom 256 segment multi-line LCD |
| Backlit |
Blue electroluminescent |
| Connection |
4mm recessed banana jacks |
| Software |
DataView® graphing, analysis and reporting software |
| Operating Temp. |
114° to 122 °F (-10° to 50°C) |
| Storage Temp. |
-40° to 158°F (-40° to 70°C) |
| Dimensions |
9.4 x 12.8 x 4.33" (240 x 185 x 110mm) |
| Weight |
7.5 lbs (3.5kg) |
| Case |
Polycarbonate |
| SAFETY |
|
| Protection |
IP54 with cover closed |
| Mechanical Shock |
EN 61557 |
| Vibration Test |
EN 61557 |
| Drop Test |
EN 61557 |
| Dielectric Test |
3kV 50/60 Hz |
| Safety Rating |
EN6101-1 50V Cat IV, Pollution Degree 2 |
| Double Insulation |
Yes |
| CE Mark |
Yes |
|
| |
| |
|
|
|
| |
| |
Specifications |
|
|
|
 |
| |
 |
| |
Related urls: |
|
|
| |
- Model 3711, [2117.60] Ground Resistance Tester (Clamp-On)
- Model 3731, [2117.61] (Clamp-On) with memory and alarm
- Model 3620, [2114.90] Ground Resistance Tester (Analog, 3-Point)
- Model 3640, [2114.92] Ground Resistance Tester (Digital, 3-Point)
- Model 6470, [2135.01] 4-Point Ground Resistance Testers
- Model 4610, [2114.94] Ground Resistance Tester (Digital, 4-Point)
- Model 4620, [2130.43] Ground Tester (Battery Powered)
- Model 4630, [2130.44] Ground Tester (Rechargeable Battery)
|
|
| |
|
| |
|
|
|
.jpg) |
|