AEMC Model 4630

Ground Tester(Rechargeable Battery)

space
Model 4630 [Catalog No. 2130.44] Ground Tester (Rechargeable Battery)
Characteristics:
  • Measures soil resistivity(4-Point) method
  • Measures ground resistance(2- and 3-Point) Fall-of-Potential method
  • Step voltage tests and touch potential measurements
  • Auto-Ranging: automatically selects the optimum range
  • Designed to reject high levels of noise interference
  • Extremely simple to operate: connect – press – read
  • LED on faceplate informs operator of high input noise, high auxiliary rod resistance and fault connections
  • AC powered with rechargeable NiMH batteries
  • Rugged, dustproof and rainproof field case
  • Can also be used for continuity tests on bonding
  • Color-coded terminals
Application:
  • Three-Point measurements of resistance to ground of ground rods and grids. Three-Point measurements are generally used when the electrode or grid can be easily disconnected, if corrosion is suspected, or in circumstances where ground faults are unlikely to occur
  • Four-Point tests or soil resistivity measurements. Locating areas of lowest soil resistivity is essential for achieving an economical grounding installation
  • Touch potential measurements, an alternative to 3-Point tests in evaluating electrical safety. This test is recommended when the ground cannot be disconnected, where ground faults are highly likely to occur, or when the “footprint” of grounded equipment is comparable to the size of the ground to be tested.
Product Description:
space
The Digital Ground Resistance Tester Model 4630 performs ground resistance and soil resistivity tests. This direct reading testers measures from   0 to 2000Ω, and is auto-ranging, so it automatically seeks outs the optimum measurement range. The Model 4630 is rugged, easy-to-use and is ideal for maintenance crews performing numerous tests. It exceeds mechanical and safety specifications for shock, vibration and drop tests called out in IEC standards. It is designed to reject high levels of interference, so it can be used under difficult conditions such as high stray currents that normally affect accuracy. The Model 4630 is powered by 9.6V, 3.5 Ah NiMH rechargeable batteries. A built-in recharge circuit, powered from 120/230V 50/60Hz line, also provides for testing while recharging.
space
Ground Kits:
space
Model 4630 Kit – 150 ft. [Catalog No. 2135.35 Ground Resistance Tester Model 4630 Kit - 150 ft.Test Kit for 3-Point testing includes two 150 ft color-coded leads on spools (red and blue), one 30 ft lead (green), two 14.5" T-shaped auxiliary ground electrodes, one set of five spaded lugs, 100 ft tape measurer and carrying bag.
space
Catalog #2135.35
space
Model 4630 Kit - 300 ft. [Catalog No. 2135.36 Ground Resistance Tester Model 4630 Kit - 300 ft.Test Kit for 4-Point testing includes instrument, two 300 ft color-coded leads on spools (red and blue), two 100 ft color-coded leads (green and black), four 14.5" T-shaped auxiliary ground electrodes, one set of five spaded lugs, 100 ft tape measurer and carrying bag.
space
Catalog #2135.36
space
Model 4630 Kit - 500 ft. [Catalog No. 2135.37 Ground Resistance Tester Model 4630 Kit - 500 ft.Test Kit for 4-Point testing includes instrument, two 500 ft color-coded leads on spools (red and blue), two 100 ft color-coded leads (green and black), one 30 ft lead (green), four 14.5" T-shaped auxiliary ground electrodes, one set of five spaded lugs, 100 ft tape measurer and carrying bag.
space
Catalog #2135.37
space
The Model 4630 is built into a double case. This extra rugged construction provides double insulation, maximum field durability and ease of serviceability.
space
Accessories (Optional)
25Ω Calibration Checker
Cat. #2130.59
Tape Measure (100 ft)
Cat. #2130.60
Ground Tester Video/Workbook set
Cat. #2130.64
space
Specifications:
space
ELECTRICAL Model 4620
Ground Resistance Auto ranging
Range 20Ω 200Ω 2000Ω
Measurement 0.00 to 19.99Ω 20.0 to 199.9Ω 200 to 1999Ω
Resolution 10mΩ 100mΩ
Open Voltage
≤42V peak
Resistance Measurement Frequency
128Hz square wave
Test Current 10mA 1mA 0.1mA
Accuracy ±2% of rdg ± 1ct ±2% of rdg ± 1ct ±2% of rdg ± 3cts
Auxilliary Electrode Influence
Current CircuitVoltage Circuit 3kΩ2000Ω 30kΩ50kΩ 50kΩ50kΩ
Interference Rejects high levels of interference voltage (DC, 50 to 60Hz, harmonics):DC voltage in series with X: 20V; AC voltage in series with Y: 13V peak;AC voltage in series with Z: 32V peak
Response Time Approximately 4 to 8 seconds for a stabilized measurement
Withstanding Voltage 250VAC or 100VDC
Power Source 120/230V 50/600HzRechargeable 9.6V, 3.5 Ah NiMH batteries
Battery Life 1800 15-second measurements (approximate)
Fuse Protection 0.1A, >250V, 0.25 x 1.25"; 30kA Interrupt Capacity
General Specifications
Display 31/2 digit, 0.71" (18mm) high; 2000-counts; electroluminescent blue backlight LCD also indicates overrange, test lead shorts and lead reversals
Backlit Blue electroluminescent
Connection 4mm recessed banana jacks
Software DataView® graphing, analysis and reporting software
Operating Temp. 114° to 122 °F (-10° to 50°C)
Storage Temp. -40° to 158°F (-40° to 70°C)
Dimensions 10.8 x 9.7 x 5.0" (273 x 247 x 127mm)
Weight 7.38 lbs (3.35kg)
Case Polycarbonate
SAFETY
Protection IP54 with cover closed
Mechanical Shock EN 61557
Vibration Test EN 61557
Drop Test EN 61557
Dielectric Test 3kV, 50/60Hz, 1 min. between four interconnected measuring terminals and any external metal ground
Safety Rating EN6101-1 50V Cat IV, Pollution Degree 2
Double Insulation Yes
CE Mark Yes
space
pdf_pic Downloads: Specifications
base
Related links:
weblink