.jpg) |
|
|
|
| |
|
| |
 |
- True RMS measurements
- Current: 1000A
- Voltage: 600V
- <31-segment analog bargraph
- Low battery indicator level check
- Audible control/warning indications
- Recording mode for Min, Max, Avg and Max Peak
- Direct reading %THD, %DF, CF, Peak (+ or -)
- Smooth function for stable readings
- Auto or manual ranging
- Peak measurements (AC or DC)(+ or -)
- Percent ripple for DC
- Auto-Off
- Designed to EN 61010, 600V Cat. III safety standards
- Includes test leads
|
|
|
|
| |
| |
|
|
|
|
| |
| |
- True RMS and DC voltage and current values
- Determine levels of voltage and current distortion
- Identify harmonic distortion patterns and source of voltage harmonics
- Locate sources of harmonic current
- Measure individual harmonics
- Identify nonlinear loads
- Prevent overheating in electrical distribution equipment, false circuit breaker tripping, power factor correction capacitor failure
- Locate overloaded neutral wires
- Derate transformers and generators to prevent overheating
- Measure crest factor to evaluate harmonic content and determine CBEMA derating factor
|
|
| |
| |
|
|
|
| |
 |
The Model F25, Harmonic Clamp-on Meter, is a portable, battery operated power quality instrument. The Model F25 performs current and voltage measurement in True RMS as well as current and voltage in DC, and immediate readings of Total Harmonic Distortion (%THD), Individual harmonic orders through the 25th, Distortion Factor (%DF), Crest Factor (CF) and Peak of distorted currents and complex voltages. Displays Min, Max, and Average measurement values allowing recording for over 24 hours with an internal clock logging record time. Frequency (Hz) can be measured through either the current or the voltage. The slim Clamp-on style makes it easy to work around crowded breaker panels and transformers.
|
|
| |
| |
|
|
|
| |
| |
| True RMS |
Model F25 |
| AC AMPERES |
|
| Measurement Range |
0.30 to 1000.0Arms; ±0.5 to ±1500.0A peak |
| Accuracy |
0.30 to 59.99A: 2% of Reading ± 20cts; 60 to 1500A peak: 2% of Reading ± 2cts |
| Crest Factor |
>5.0 below 300A |
| Frequency Range |
0.5Hz to 5kHz |
| AC VOLTAGE |
|
| Measurement Range |
0.05 to 600Vrms; ±0.05 to ±1500V peak |
| Accuracy |
0.05 to 59.99V: 1% of Reading ± 10cts; 60 to 1500V peak: 1% of Reading ± 2cts |
| Input Impedance |
1MΩ |
| Frequency Range |
0.5Hz to 5kHz |
| DC AMPERES |
|
| Measurement Range |
±0.10 to 1500.0A |
| Accuracy |
±0.30 ± 1500.0A |
| Basic Accuracy |
0.30 to 59.99A: 2% of Reading ± 20cts; 60 to 1500A: 2% of Reading ± 2cts |
| DC VOLTS |
|
| Measurement Range |
±0.05 to ±600V |
| Accuracy |
0.05 to 59.99V: 1% of Reading ± 10cts; 60 to 1500V peak: 1% of Reading ± 2cts |
| Input Impedance |
1MΩ |
| TOTAL HARMONIC DISTORTION (%THD) |
| Range |
0.2% to 1000% |
| Resolution |
0.1% |
| Accuracy |
5% of Reading ± 2cts |
| Frequency Range |
Fundamental 40Hz to 70Hz |
| Display |
Digital: %THD and True RMS (A or V)
Bargraph: True RMS (A or V) |
| DISTORTION FACTOR (%DF) |
| Range |
0.2% to 100% |
| Resolution |
0.1% |
| Minimum Input |
10V or 10A |
| Basic Accuracy |
5% of Reading ± 2cts |
| Frequency Range |
Fundamental 40Hz to 70Hz |
| Display |
Digital: %DF and True RMS (A or V)
Bargraph: True RMS (A or V) |
|
|
| |
| General Specifications |
| INDIVIDUAL HARMONICS |
| Range |
0.2% to 300% (%THD or %DF) |
| Rank |
Hdc (DC component), H01 to H25 |
| Resolution |
0.1% |
| Accuracy |
Distortion >10% & rank <H13: 5% of Reading ± 2cts
Distortion >10% & rank >H13: 10% of Reading ± 2cts
Distortion <10% & rank <H13: 10% of Reading ± 2cts
Distortion <10% & rank >H13: 15% of Reading ± 2cts |
| Frequency Range |
Fundamental 40Hz to 70Hz, 25th order |
| Display |
Digital: %THD and Individual; Harmonic value (A or V); Bargraph: True RMS (A or V) |
| TRANSFORMER HARMONIC DERATING FACTOR (CBEMA THDF) |
| Range |
0.10 to 1.00 |
| Resolution |
0.01 |
| Basic Accuracy |
2% of Reading ± 2cts |
| Display |
Digital: THDF; Bargraph: Arms |
| TRANSFORMER K-FACTOR RATING |
| Range |
1 to 30 |
| Resolution |
0.1 |
| Basic Accuracy |
1 to 9.9%: 5% of Reading ± 2cts; 10 to 30: 10% of Reading ± 2cts |
| Display |
Digital: %THD or K Factor; Bargraph: Arms |
| RIPPLE |
|
| Range |
1% to 999.9% |
| Resolution |
0.1% |
| Basic Accuracy |
2 to 99.9%: 5% of Reading ± 10cts; 100 to 999.9%: 5% of Reading ± 2cts |
| Display |
Digital: % Ripple; Bargraph: DC (A or V) |
| CREST FACTOR (CF) |
| Range |
1.00 to 10.00 |
| Resolution |
0.01 |
| Minimum Input |
>5V or >5A |
| Basic Accuracy |
(40 to 70Hz):
1.00 to 3.50: 2% ± 2cts
3.51 to 5.99: 5% ± 2cts
6.0 to 10.0: 10% ± 2cts |
| Display |
Digital: CF Bargraph: TRMS (A or V) |
| FREQUENCY (HZ) |
| Range |
0.5 to 20,000Hz |
| Minimum Input |
2A or 2V |
| Basic Accuracy |
0.5Hz to 999.9Hz: 0.1% of Reading ± 2cts
1000Hz to 9999Hz: 0.2% of Reading ± 2cts
10kHz to 20kHz: 0.5% of Reading ± 2cts |
| Display |
Digital: Hz; Bargraph: DC (A or V), TRMS (A or V) |
|
| |
| |
|
|
|
| |
| |
Specifications |
|
|
|
 |
| |
 |
| |
Related urls: |
|
|
| |
- Model 500 , (AC, 400AAC, 600VAC, Ohms, Continuity)
- Model 501 , (AC, 400AAC, 600VAC/DC, Ohms, Continuity)
- Model 502 , (TRMS, 400AAC, 600VAC/DC, Ohms, Continuity)
- Model 503 , (AC/DC, 400AAC/DC, 600VAC/DC, Ohms, Continutiy)
- Model 511 , (AC, 1000AAC, 1000VAC/DC, Ohms, Continuity)
- Model 512 , (TRMS, 1000AAC, 600VAC/DC, Ohms, Continuity)
- Model 514 , (AC/DC, TRMS, 1000AAC/DC, 600VAC/DC, Ohms,
Continuity)
- Model F1N ,(AC, TRMS, 400A, Hz)
- Model F3N , (AC, TRMS, 400A, Hz, Peak, Smooth, Min/Max)
- Model F01 , (TRMS, 400AAC, Ohms, Continuity)
- Model F03 , (TRMS, 400AAC/DC, 600VAC/DC, Ohms, Continuity, Temp.)
- Model F05 , (TRMS, 400AAC/DC, 600VAC/DC, Hz, Power (kW), Phase Rotation, Ohms, Continuity)
- Model F07, (TRMS, 400AAC/DC, 600VAC/DC, Hz, Ohms, Continuity, Temperature)
- Model F25 , (TRMS, 600VAC/DC & 1500AAC/DC)
- Model 721 , (9999-count, TRMS, V, A, F, Hz, THD, CF)
|
|
| |
|
| |
|
|
|
.jpg) |
|